The JA-82Y GSM communicator installers manual 

13/13 

MDL51109 

 
 

Tab. 7 communicator programming sequence continues 

 

Function  

Sequence 

Possible options 

Factory default settings 

ARC main  telephone number / IP address 
/ URL  

01 p xx..x 

p=1  ARC1,  p=2  ARC2,  p=3  IMG,  xx..x  =  tel. 
number max. 30 digits. When using IP protocol, IP 
or  URL  addresses  are  entered  instead  of 
telephone numbers 

– see URL command 

To erase the corresponding telephone numbers or 
URL addresses enter 01p*0 

erased 

ARC  backup  telephone  number  /  IP 
address / URL  

02 p xx..x 

p=1  ARC1,  p=2  ARC2,  p=3  IMG,  xx..x  =  tel. 
number max. 30 digits. When using IP protocol, IP 
or  URL  addresses  are  entered  instead  of 
telephone numbers 

– see URL command 

To erase the corresponding telephone numbers or 
URL addresses enter 02p*0    

erased 

Main ARC URL address setting  

See ARC main telephone number / IP address / URL 

Performed via OLink software or by SMS instruction 

code

 

URL p xxxxxxx : pppp

 where p=1 ARC1, p=2 ARC2, p=3 IMG, xx..x = 

URL  address,  pppp  =  port  address  (not  required)..  SMS  instruction  example:   

URL  1 

www.arc1.com

  :  08080

      To  erase  the 

addresses key in 01p

0, 02p

0 or ARC telephone number    

Installation (alarm system) ID for ARC use  

03 p zz..z

p=1  ARC1,  p=2  ARC2,  p=3  IMG,  xx..x  = 
installation  number  max.  8  characters  0  to  9  and 

1=A to 

6=F 

0000 

Selecting 

the 

ARC 

communication 

protocol 

04 p x 

p=1 ARC1, p=2 ARC2, p=3 ARC3(IMG) 
x=0 CID,  
x=1 Jablotron IP,  
x=2 Jablotron SMS, 
x=5 IMG 

– Jablotron image server 

1 Jablotron IP 

2 Jablotron SMS 

Selection of events to report to ARCs 

05 p uu x 

p=1 ARC1, p=2 ARC2 
uu is an event code (see 7.4) 
x=1 report, x=0 no report   

All events are reported - see tab. 3 

Periodic or fixed ARC connection check   

06 p x 

p=1 ARC1, p=2 ARC2 
x=0 with a period from the last report according to 
the 07 p hhmm setting  
x=1  once  a  day  at  the  time  set  by  entering  07  p 
hhmm    

With a period after the last report  (X=0) 

ARC communication checking period 

07 p hhmm 

p=1 ARC1, p=2 ARC2 
hhmm = hours, minutes, see setting via 06 p x  

2359 

Enable  ARC  reporting  (ARC2  backs  up 
ARC1)  

08 p x 

p=1 ARC1, p=2 ARC2 
x=0  reports  disabled,  x=1  reports  enabled,  
x=2  only  for  ARC1,  sets  that  ARC2  backs  up 
ARC1  

1,2 ARC reporting disabled 

3 enabled (IMG) 

Recording  reports  sent  to  ARCs  in  the 
control panel memory 

001 x 

x=0 no (only records ARC communication faults)  
x=1 yes (all reports except communication checks)  

no 

Indicate  an  ARC  communication  fault  if  a 
report  is  not  successfully  received  within 
110 sec of transmission 

002 x 

x=0 no 
x=1 yes 

no 

Remote access password  

894 xxx …x 

1-32 characters, (only numbers are available when 
using keypad) 

1234ABCD 

Locking the ARC settings 

091 xx..x

xx..x is your code (4 to 8 digits) 
Entering this code and then exiting service mode 
will lock the ARC settings 
091*0 will erase the code (permanently unlocked) 

unlocked 

Unlocking the ARC settings 

092 xx..x

xx..x is the locking code used by sequence 091 

ARC programming can be temporarily enabled in 

service mode by entering this sequence. It will then 

relock on exiting service mode. For permanent 

unlocking see sequence 091. 

Period  of  waiting  before  repeating 
unsuccessful communication to the ARC  
 

0001 p mmss 

p=1 ARC1, p=2 ARC2 
mmss = minutes, seconds 

0015 

Number  of  repeated  attempts  after 
unsuccessful communication to the ARC 

0002 p n 

p=1 ARC1, p=2 ARC2 
n= 1x to 9x 

2x 

 
 

Содержание JA-82Y

Страница 1: ...commend blocking the roaming feature in the SIM card to avoid unnecessarily high communication fees contact your GSM provider for details 3 User functions of the communicator The following text describes all communicator features The installer should show the end user how to operate the functions used in the particular installation 3 1 Event reporting to the user s phone The communicator reports e...

Страница 2: ...M8 To program phone numbers to the M memories enter the following sequence while in Maintenance Service mode 81 M xxx x y 0 where M is memory number 1 to 8 xxx x is a telephone number max 20 digits y is a sequence for control via unanswered calls it does not have to be entered In a split system information from all sections ABC is reported to the 1st and 8th number positions sections AC to numbers...

Страница 3: ...2 is programmed the code 2222 will be automatically inserted in an SMS with instructions sent from the first number stored in the memory Factory default setting No code 6 7 Allowing remote access for telephone numbers Remote access is allowed for numbers saved in positions 1 to 8 Programming sequence 85 M x where M memory position tel numbers 1 to 8 x parameter 1 to allow access parameter 0 to den...

Страница 4: ...ation off 907 1 synchronization on Factory default settings on 6 18 Phone receiver loudness To set the loudness of the receiver of the phone which is used to call the communicator key in 909 x where x is a number from 1 to 9 max Factory default setting 9 max 6 19 Number to be called to maintain SIM card validity If a prepaid SIM card is used and a lack of outgoing phone calls for a certain period ...

Страница 5: ...o the communicator turn on the control panel power and then enter the correct PIN code 920 PIN 0 and wait until the communicator registers to the GSM network its red LED should turn off within a minute The communicator memorizes the set PIN and it will use it automatically whenever it registers to the GSM network again If you are replacing the SIM card in the communicator with another one and the ...

Страница 6: ... 97 Low SIM card credit balance Not reported 50 SMS transmission from a line e g from JA 84P Not reported 51 ARC communication failure 1354 reported 52 ARC communication restored 3354 reported 53 tab 3 ARC event table Source Name 701 Control panel 731 Communicator 741 Keypad 001 050 Device 1 Device 50 500 Master code 599 Service code 501 550 Code 1 code 50 tab 4 Source number table The report to t...

Страница 7: ...ated by green LED 1 being permanently lit on the left under the SIM card holder see fig 1 Communicator description Transmission to the server is signalled by a flashing green LED Successful transmission is confirmed by a long green LED flash and unsuccessful transmission is reported by rapid flashes of the green LED Successful transmission from the GSM communicator to the server is confirmed by a ...

Страница 8: ...ed in position 0 by the sequence 81 0 xxx x 0 xxx x own telephone number If you change the SIM card position 0 will be automatically erased Time synchronization see section 6 17 of the control panel is performed whenever entering into service mode or maintenance mode and if there is a difference greater than 5 minutes between the correct time and control panel time synchronization is performed aut...

Страница 9: ... Incoming call Welcome to OASiS Enter your access code Valid code CODE Can t perform the operation Enter your access code OK Invalid Valid Disarmed system Press 1 to arm OK System Armed Armed system Press 2 to disarm OK System disarmed Service mode If the system is in the requested state terminate the call The 9 key pressed Keypad simulation ...

Страница 10: ...witching to service maintenance mode 7 other event 66 Exiting service maintenance mode 7 other event 67 End of alarm indication 7 other event 78 Alarm cancelled by user S S S S S S S 7 other event 79 Control panel reset 7 other event 80 All tampers on standby 7 other event 81 All faults removed 7 other event 82 System power supply OK 7 other event 83 The communicator has no connection 5 fault 84 C...

Страница 11: ... 702 Finish setting 406 Service mode 529 Internal communication error 703 Signal strength 407 Maintenance mode 530 Internal communication restored 704 Control 409 Battery discharged 531 Communication test 705 Bypass 410 Tamper alarm 532 Unconfirmed alarm 706 Test OK 411 Alarm memory 533 Blocking after an alarm 707 Test error 412 Fault 534 Unblocking after an alarm 708 0 4 413 Power supply fault 53...

Страница 12: ...abled Enabling remote access 802 x x 0 no x 1 yes by phone and Internet x 2 yes but only by enrolled phones 1 yes Forwarding of incoming SMS messages 801 x x 0 no x 1 if the incoming text is not an SMS instruction it will be forwarded to the first programmed number in memories M1 to M8 yes Autoconfiguration of GPRS 903 x X 0 autoconfiguration disabled x 1 autoconfiguration enabled Autoconfiguratio...

Страница 13: ...vent code see 7 4 x 1 report x 0 no report All events are reported see tab 3 Periodic or fixed ARC connection check 06 p x p 1 ARC1 p 2 ARC2 x 0 with a period from the last report according to the 07 p hhmm setting x 1 once a day at the time set by entering 07 p hhmm With a period after the last report X 0 ARC communication checking period 07 p hhmm p 1 ARC1 p 2 ARC2 hhmm hours minutes see setting...

Отзывы: