Configuration
19 (28)
6.5
Protocol Specific Restrictions
For information about the setting possibilities of the individual protocols see
WEB-PLC —
Online Help — I/Os
.
The number of devices and values that can be defined in the various protocols is limited.
Modbus
•
Client: 128 devices, 4096 values (max. 8129 array elements)
•
Server: 4096 values (max. 8129 array elements)
•
TCP Server/Slave: up to 16 Modbus TCP Client/Master can be connected
•
RTU Slave: one Modbus RTU Master and 4096 values can be connected
•
RTU Master: up to 128 devices and 4096 values can be connected
IEC 60870-5-104
•
Client: 32 devices, 4096 values (max. 8129 array elements)
•
Server: 4096 values (max. 8129 array elements)
IEC 61850
•
Client: 128 devices, 4096 values
•
Server: 4096 values
SNMP
•
up to 128 agents and 4096 values
PROFIBUS
•
up to 128 modules and 244 values (per direction)
PROFINET
•
up to 128 modules and 1440 values (per direction)
EtherNet/IP
•
up to 128 modules and 1448 values (per direction)
SG Gateway User Manual
4.04.0450.20000 1.3