Information/Alarms

6 720 645 172 (2010/07) en

36

5.6.45 Short oper. time in heating mode (C)
Function:

 Compressor operation for heating is on 

average shorter than 10 min per start based on a 
minimum of 5 starts within 24 hours. The alarm resets 
automatically at midnight.

Heat pump:

 All.

B

Check that the heating system is correctly installed.

B

Check that the installation is correctly dimensioned.

B

Check that any flow adjustments are correctly 
implemented.

5.6.46 Temporary error G2 heat carrier pump (C)
Function:

 The circulation pump has given an error signal 

for less than 3 minutes.

Heat pump:

 All.

Not displayed in the alarm list.

5.6.47 Temporary error G3 coll. circuit pump (C)
Function:

 The circulation pump has given an error signal 

for less than 3 minutes.

Heat pump:

 All.

Not displayed in the alarm list.

5.6.48 Control unit restarted (C)
Function:

 The control unit restarted due to insufficient 

voltage.

Heat pump:

 All.

B

Check the voltage to the heat pump and 24Vac.

5.6.49 Replace memory battery (C)
Function:

 The battery voltage has fallen. If the supply 

voltage disappears when the battery is empty there is a 
risk that the control unit will lose software, which will 
require reloading.

Heat pump:

 All.

B

Replace the battery (replacement battery CR2032).

5.6.50 Start-up attempt interrupted (C)
Function:

 At compressor start the temperatures and 

pressure switches are checked. When one of these is not 
approved by the control unit the start attempt is 
cancelled. A new start attempt occurs after 20 min if a 
demand arises.

B alarm is activated when the alarm has occurred more 
than once during the last 120 minutes (

Æ

 Chapter 

5.6.22, page 33).

Heat pump:

 All.

Not displayed in the alarm list.

5.6.51 Accessory x temp. deviation (C)
Function:

 The measured temperature differs from the 

set point value by more than the set limit (10 K) for more 
than 30 minutes.

The limit is set under 

Accessories

 (

Deviation

).

Heat pump:

 E21.

B

Check the settings for the accessory 
(

Æ

 Table 37, page 21).

B

Check that the set point value is reasonable.

B

Check the installation of the sensor.

B

Check the connection, measure the resistance and 
compare with the resistance table.

5.6.52 Hot water oper. stoppad T8 (C)
Function:

 During hot water production T8 heat transfer 

fluid out has risen above its permitted max limit 65 °C. 
Hot water production is stopped.

Heat pump:

 Heat pump that makes hot water.

Not displayed in the alarm list.

B

Check the flows and valves.

B

Check the installation of the sensor.

B

Check the connection, measure the resistance and 
compare with the resistance table.

NOTICE: 

Watch out for ESD damage to the 

electronics.

B

Ensure that ESD damage is avoided when 
replacing the battery.

Содержание Rego 5101

Страница 1: ...Installation Manual Rego 5101 ok 6 720 641 739 37 1I 6 720 645 172 2010 07 en...

Страница 2: ...nication 10 4 2 Settings Addressing 11 4 3 Settings Room temperature 11 4 4 Settings Additional heat 14 4 5 Settings Hot water 18 4 6 Settings Accessories 21 4 7 Settings Circulation pumps 24 4 8 Sett...

Страница 3: ...hildren never operate this appliance unsupervised or play with it B Ensure that only personnel who can operate this appliance correctly have access to it Service and maintenance B Only qualified perso...

Страница 4: ...Low pressure switch E2x Di8 RHP High pressure switch E2x Di7 8 K11 Safety switch E2x Tab 3 Potential free digital inputs 24Vac Analogue outputs 0 10Vdc HP Ao1 E71 E1 Q71 E51 Q51 Additional heat mixin...

Страница 5: ...u display in order to See information from the heat pump See available menus Change set values 3 5 Return button Use to Go back to the previous menu level Leave a setting display without changing the...

Страница 6: ...Initial menu to move to the top menu level Customer B Use and to scroll between the available menus at menu level Navigate between the menus Change a value e g heat curve at 0 C The heat curve is only...

Страница 7: ...rn without saving Place a decimal point in a value B Press so that the cursor is placed to the right of the last digit in the value and press A decimal point is included Press and use or to set the de...

Страница 8: ...g The compressor is blocked via external control Off The compressor is not running E11 G1 is running in case of winter operation or anti seizure operation Q21 E4x Q1x is active in case of emergency op...

Страница 9: ...r 5 seconds in the Initial menu Log in as installer B Enter password mmdd under Access level mm current month dd current day E g 0315 15th March Logging out B Use function Quick log out on installer l...

Страница 10: ...at pump in which the function is available 4 1 Communication Settings at customer level are in the User Manual for Greenline HE Always set E21 first Most settings are made here because for example Add...

Страница 11: ...temperature at which winter operation shall start directly without a delay Delays prevent repeated stops and starts of the heating system circulation pump when the outdoor temperature fluctuates abov...

Страница 12: ...ms with normal flow For low flow systems Min 3 K Max 16 K is recommended For high flow systems floor heating Min 1 K Max 4 K is recommended B Set the minimum and maximum hysteresis and time factor for...

Страница 13: ...t value The heat pump that has been out of operation the longest starts first that which has operated longest stops first 4 3 3 Heating demand The heating demand is activated in each heat pump when E1...

Страница 14: ...ngs Start E2 E1 Hysteresis Delay Actual v 3 K 180 min Display can be changed E21 Start E2 E2 Delay Actual v 60 min Display can be changed Start E2 E3 Delay Actual v 60 min Display can be changed Stop...

Страница 15: ...Start E51 Hysteresis Delay Actual v 3 K 180 min Display can be changed E21 Stop E51 Delay Actual v 10 min Display can be changed PID E51 P I D T1 Sp Out 1 100 0 Display B Set conditions for engaging...

Страница 16: ...added continuously When the sum Setting Factory Range HP Additional heat Additional heat type No additional heat Comp add heat No additional heat Internal add heat District heating Modulated add heat...

Страница 17: ...alue set in Delay 180 min the additional heat is activated The additional heat and any internal circulation starts When the thermostat E71 E1 P111 acknowledges that the additional heat has reached its...

Страница 18: ...en the heat pump receives values for the hot water temperature from the previous heat pump B Select Communicated when the heat pump has all information about the hot water temperature and start stop l...

Страница 19: ...he maximum number of degrees K the flow temperature T1 may exceed its set point value and how many degrees K T1 may increase during hot water production When both conditions are fulfilled the heat pum...

Страница 20: ...arises when T3 falls below its start temperature and ceases when T3 exceeds its stop temperature With a local sensor T9 must also exceed the stop limit 4 5 3 Emergency operation hot water If the func...

Страница 21: ...Use and to scroll through the settings In Room sensor Room sensor Actual v Display E21 In Active room sensor Active room sensor Actual v Set point Average Display 22 C Display E21 B Set the set point...

Страница 22: ...values for P and I B Set the temperature deviation that shall cause an alarm Accessory x temp deviation Chapter 5 6 51 page 36 B Enter pump function Winter means that the accessory circulation pump i...

Страница 23: ...nnected mixing valve to maintain the stated fixed set point value In Own heat curve Set point curve E21 B Set the set point value for the circuit flow at different outdoor temperatures For the heat cu...

Страница 24: ...T8 T9 Heat DHW At Fixed speed Fixed speed Heat DHW Regulating 7 K 7 K 100 100 Regulating Fixed speed 5 10 K 5 10 K 30 100 30 100 E2x B Set how G2 should function B In Regulating Set the temperature d...

Страница 25: ...ry Range HP External control External input B11 Select function Block all No effect Block all Block add heat Block compressor Block hot water Start comp add heat Start compressor E2x B Select the func...

Страница 26: ...ction test all inputs and outputs in conjunction with commissioning B Set Auto after completed test Otherwise an alarm occurs Output in wrong pos after function test Chapter 5 6 30 page 34 The control...

Страница 27: ...eration Additional heatfor the time after reset Additional heat is displayed in E21 Alarm settings E2x B Indicate Yesif short run time will be monitored for Heatingand or Hot water Information alarm S...

Страница 28: ...ory reset Factory reset Reset Confirm No No No Yes No Yes E2x B Indicate Yes to reset all values to the factory setting Customer settings can be affected if the heat curve is changed by the reset E21...

Страница 29: ...ble alarms With Information category C no indication is given 5 4 Alarm list and Alarm history When a disturbance occurs a fault message is stored in the alarm list and alarm history The alarm list is...

Страница 30: ...the control unit Heat pump E21 B Check the installation of the sensor B Check the connection measure the resistance and compare with the resistance table B Replace the sensor if necessary 5 6 4 Failur...

Страница 31: ...erating error G3 Heat pump All B Interrupt the current for at least 5 seconds to reset the alarms Chapter Resetting the pump alarm in the installation guide for the heat pump B Check that the circulat...

Страница 32: ...ature B Check the collector circuit B Check the particle filter and clean if necessary B Check the valves and any distributors B Check that the sensor shows correct temperature compare with resistance...

Страница 33: ...th resistance table 5 6 22 Start up attempt interrupted B Function At compressor start the temperatures and pressure switches are checked When one of these is not approved by the control unit the star...

Страница 34: ...y functions are active When a safety function is activated all outputs are reset to Auto Heat pump All 5 6 31 Hot water in emerg oper C Hot water sensor T3 is not functioning and the heat pump has swi...

Страница 35: ...ance table B Check heat carrier pump G2 5 6 41 High temp diff heat transfer fluid C Function The difference T8 T9 exceeds 15 K after 15 minutes of compressor operation Heat pump All B Clean the partic...

Страница 36: ...acement battery CR2032 5 6 50 Start up attempt interrupted C Function At compressor start the temperatures and pressure switches are checked When one of these is not approved by the control unit the s...

Страница 37: ...1 5 8 968 7 21 1081 8 50 1194 0 79 1305 1 108 1415 3 7 972 6 22 1085 7 51 1197 8 80 1308 9 109 1419 1 6 976 5 23 1089 6 52 1201 6 81 1312 7 110 1422 9 5 980 4 24 1093 5 53 1205 5 82 1316 6 111 1426 6...

Страница 38: ......

Страница 39: ......

Страница 40: ......

Отзывы: