I/O connections
6 720 645 172 (2010/07) en
4
2
I/O connections
Temperature inputs PT1000
HP
Ai1
E11.T1
Flow
E21
Ai2
E10.T2
Outdoor
E21
Ai3
E4x.T3
Hot water
E2x
Ai4
T6
Hot gas
E2x
Ui1
T8
Heat transfer fluid
out (flow from heat
pump)
E2x
Ui2
T9
Heat transfer fluid
in (return to heat
pump)
E2x
Ui3
T10
Collector circuit in
E2x
Ui4
T11
Collector circuit out
E2x
Tab. 2 Temperature inputs PT1000
Potential-free, digital inputs 24Vac
HP
Di1
IND/SSM
E11.G1
Signal circulation
pump heating
system
E21
Di2
B11
EVU / External
control
E2x
Di3
E71.E1.B31
E51.B11
E2.F21
Thermostat
Differential
pressure monitor
Additional heat
alarm
E21
Di4
E1 IND
Operating reply
compressor
E2x
Di5
G2.F13
Motor cut-out heat
transfer fluid pump
E2x
Di6
G3.F13
Motor cut-out
collector circuit
pump
E2x
Di7
RLP
Low pressure
switch
E2x
Di8
RHP
High pressure
switch
E2x
Di7+
8
K11
Safety switch
E2x
Tab. 3 Potential-free, digital inputs 24Vac
Analogue outputs 0-10Vdc
HP
Ao1
E71.E1.Q71
E51.Q51
Additional heat
mixing valve,
heating system
E21
Ao2
Ao3
Ao4
G2
Heat carrier pump
E2x
Ao5
G3
Collector circuit
pump
E2x
Tab. 4 Analogue outputs 0-10Vdc
Digital outputs 230Vac
HP
Do1
E1
Compressor
E2x
Do2
E71.E1
E2.E1
Start additional heat
Internal electric
additional heat stage
1
E2x
Do3
E2.E2
Internal electric
additional heat stage
2
E2x
Do4
E4x.Q1x
Q21
3-way valve hot water
External
Internal
E2x
Tab. 5 Digital outputs 230Vac
Digital outputs potential-free (inverted)
HP
Do5
E11.G1
Circulation pump,
heating system
E21
Do6
E71.E1.G71
E31.G33
Circulation pump
mixed additional
heat
External collector
circuit pump
E21
E2x
Do7
P2
General alarm (A/
AB)
E2x
Tab. 6 Digital outputs potential-free (inverted)
Accessories
Quantity
HP
Mixing valve/Pool/Room
sensor (Multi-regulator)
0-9
E21
Tab. 7 Accessories