Operation Manual - Hobart 2400 Compact – 120 / 140 / 180 kVA
Operator’s Instructions
Document no. 578.430AB
Page 51 of 75
6.4
Default Factory Settings:
Output Voltage (V):
115.0
Compensation Type:
Manual (Plug & Play if GPU supplied with cables)
Output 1 Compensation (V):
0.0 (Set if the GPU is supplied with cable)
Output 2 Compensation (V):
0.0 (Set if the GPU is supplied with cable)
Output Mode:
Individual (Depending on configuration)
Fan Control:
Normal
Remote Stop:
Normally Closed for units shipped/built in the America’s
EF Interlock:
Bypassed (Active if GPU supplied with cables)
EF Interlock Ripple Level (V):
20.0
EF Interlock Delay (sec.):
3.5
Aircraft Connector detection:
Disabled
(Enabled if supplied with cable & 90% Switch/split “F” pin)
GPU Enable:
Bypassed
Door Switch:
Bypassed (Active with option 578853)
Plug Temperature:
Normally Open
Neutral Voltage Supervision (V):
42.0
Earth Leakage Level (A):
15.0
Earth Leakage Delay (ms):
1000
Real Time Clock Setup:
Actual (Manufacturer’s location)
Ethernet Configuration:
192.168.1.100
Modbus Slave Address:
1
LED Brightness:
Medium
Date/Time Format:
HH:MM:SS & DD:MM:YYYY
Unit of Measure:
Metric
Language:
Actual
OM2252
Rev 0 December 15 2016