Operation Manual - Hobart 2400 Compact Power – 120 / 140 / 180 kVA
Transport and Installation
Document no. 578.430AB
Page 27 of 75
RJ45 connector
4.10 TCP/IP On-board Interface
The AXA 2400 is equipped with a TCP/IP (RJ45)
communication port for supervision and monitoring of the
Ground Power Unit (GPU) e.g. by the means of a central
computer. The port is located on the Control Board (A1).
The protocol is limited to MODBUS TCP/IP. The data
available from the GPU is comprehensive and should meet
most requirements.
Supported Modbus Function Codes
The AXA 2400 implements a subset of the Modbus
Application Protocol Specification V.1.1b.
The following function codes are supported in Modbus requests:
-
03 (0x03) Read Holding Registers
-
04 (0x04) Read Input Registers
-
06 (0x06) Write Single Register
-
16 (0x10) Write Multiple Registers
In the following section, the different kinds of data available are:
•
System in use, system in standby and system in fault.
•
The GPU provides a comprehensive range of internal and external parameter measurements and
information e.g. voltages, currents, temperatures, time, date etc.
•
The GPU provides two kinds of logs:
•
The Black Box which contains the last 100 errors detected together with all relevant parameters
and status information available in connection with a shut-down.
•
The Power log which contains the time in use and the power consumption for the last 100
operations.
Note!
Detailed information on the Modbus Communication and available parameters can be found in the
document 999.008, which can be obtained from ITW GSE AXA Power on request.
Please refer to section 6.3 for communication set-up.
OM2252
Rev 0 December 15 2016