4.3.

 Check to insure all piping connections are 

tight. The pipes should be supported by 

fastening to floor joists or wall. This will 

prevent the pump from moving in the sump. 

If it moves the switch could get stuck and 

either keep the pump running or not let it 

turn on.

4.4.

 The power to the outlet should be Off at 

this point. The dedicated outlet should sup-

ply power only to the pump.

4.5.

 Our sump pumps have either a single power 

cord for pumps with built-in switches or 

two power cords for pumps with piggyback 

switches: 

Built-In/Single Cord

 - plug the single power 

cord into a dedicated power outlet. 

Piggyback/Two Power Cords

 - insert the pig-

gyback switch male plug into a dedicated 

power outlet. You then plug the standard 

male pump plug into the back, female side, 

of the piggyback switch plug. 

4.6.

 Fasten the power cords to the discharge 

pipes using tie wraps or electrical tape. Coil 

and store any excess power cord outside the 

sump. 

5. OPERATION
5.1.

 Turn the power On at the breaker panel 

and/or the disconnect switch.

5.2.

 Fill the basin with water and observe where 

the pump turns On and Off. It should go On 

well before the water overflows the top of 

the sump. The pump should go Off before 

the water goes below the pump suction. The 

On-Off cycle on models with wide-angle 

float switches is adjustable. Adjustment is 

made by changing the tether length between 

the switch body and the switch tether (pivot) 

point. The tether length cannot be less than 

3” – 3.5”. Tethers less than 3” may not allow 

the float to drop down enough to turn off. 

See "Installation Data"

.

5.3.

 

Install a cover on the sump 

basin if there is a danger 

of debris, children, or pets falling into the 

basin. 

See Basin “Style” in Section 2.3

.

6. SEASONAL SERVICE / MAINTENANCE
6.1.

 If your sump pump only operates seasonally 

and then sits idle for months it is recom-

5. OPERATION

6. SEASONAL SERVICE / MAINTENANCE

mended that you test the pump before your 

rainy season begins. Fill the sump with water 

and check for debris and proper switch 

operation. Remove any debris which could 

clog the suction strainer or jam the switch. 

Insure that the switch operates freely and 

does not hit the sump wall or hang-up on 

piping or power cords.

7. OPTIONS
7.1.

 Your pump supplier has a full line of basins, 

covers, high water alarms, and battery back-

up pump systems available to complete your 

system. We also sell simplex and duplex  

pump control panels. A duplex system is 

recommended when the inflow is constant 

and the pumps run almost continuously. The 

duplex system provides a back-up pump in 

the event the primary pump fails.

8. TROUBLE SHOOTINg CHART

Extreme caution should be exercised when ser-

vicing electrical devices. Fatal injuries could re-

sult from electrical shock. Always disconnect the 

electrical power from the device being serviced 

unless it is necessary for the work being done.
MOTOR NOT RUNNINg 

(See causes 1, , 3, , 6, 8)
LITTLE OR NO LIqUID DELIVERED 

(See causes 5, 6, 7, 8, 10)
PUMP WILL NOT TURN OFF 

(See causes 7, 8, 9, 10, 13)
PUMP CYCLES CONSTANTLY

 (See causes 9, 11, 1, 13)
PRObAbLE CAUSES:

  1. Tripped thermal protector.

  . Open Circuit breaker of blown fuse.

  3. Rotating parts binding.

  . Defective motor.

  5. Air locked.

  6. Low voltage.

  7. System head too high. 

  8. Pump clogged.

  9. Level control defective or switch not 

      properly positioned.

10. Improper check valve direction.

11. Check valve leaking.

1. Incorrect size basin or wet-well.

13. Inflow excessive for size of pump.

8. TROUBLE SHOOTINg CHART

7. OPTIONS

WARNING

Содержание Goulds Pump SP02

Страница 1: ...onstruction Stainless Steel motor casing and fasteners Glass filled thermoplastic impeller and casing Bearings Upper and lower heavy duty ball bearing construction Motor is permanently lubricated for...

Страница 2: ...three prong grounding plug 115V AGENCY LISTINGS APPLICATIONS Specially designed for the following uses Basement draining Water transfer Dewatering SPECIFICATIONS Pump Discharge size SP024 11 4 NPT SP...

Страница 3: ...m Float Switch Cord Discharge Min Min Minimum Maximum Shipping Order No HP Volts Amps Circuit Phase Style Length Connection On Off Basin Solids Weight Breaker Level Level Diameter Size lbs kg SP024V 1...

Страница 4: ...d the ITT Engineered Blocks Symbol are registered trademarks and tradenames of ITT Corporation SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE BSP02 03 August 2006 2006 ITT Corporation Engineered...

Страница 5: ...lds Pumps Sump Pumps Installation Operation and Maintainence Instructions Goulds Pumps is a brand of ITT Water Technology Inc a subsidiary of ITT Industries Inc www goulds com Engineered for life Wast...

Страница 6: ...rformed by a qualified technician Always follow the National Electrical Code NEC or the Canadian Electrical Code as well as all local state and provincial codes The pump must be connected to a dedicat...

Страница 7: ...never by the power cord Place the pump against the basin wall so the switch is to the center See Installation Data 3 Piping 4 INSTALLATION IN SUMP 1 GENERAL INFORMATION 1 1 Sump pumps are designed to...

Страница 8: ...debris children or pets falling into the basin See Basin Style in Section 2 3 6 SEASONAL SERVICE MAINTENANCE 6 1 If your sump pump only operates seasonally and then sits idle for months it is recom 5...

Страница 9: ...Vertical Switch 12 8 5 2 No Switch Manual Manual 9 115 7 1 LSP07 10 1 20 1 Wide Angle Switch 12 5 6 5 12 3 8 15 6 8 230 3 5 SP024 2 4 1 SP025 10 1 Vertical Switch 10 6 3 9 3 8 SP035 1 3 115 3 0 1 8 3...

Страница 10: ...Figure 6 Pumpmaster and Pumpmaster Plus Hard Wired Figure 4 Tether length INSTALLATION DATA INSTALLATION DATA Typical Pump Installation in Sump Figure 3 PUMP ELECTRICAL PLUG CHECK VALVE PIGGYBACK SWI...

Страница 11: ...mages of any kind and e Reimbursement for loss caused by interruption of service For purposes of this warranty the following terms have these definitions 1 Distributor means any individual partnership...

Страница 12: ...umps Bombas para sumideros Manual de Instalaci n y Operaci n Goulds Pumps son una marca de f brica de ITT Water Technology Inc un subsidiario de ITT Industries inc www goulds com Engineered for life A...

Страница 13: ...mpre siga el C digo El ctrico de EE UU NEC o el C digo El ctrico Canadiense adem s de todos los c digos locales estatales y provinciales La bomba debe conectarse a un circuito el ctrico dedicado prote...

Страница 14: ...que la bomba se bloquee con aire La no perforaci n de este orificio es una de las 3 TUBER AS 1 INFORMACI N GENERAL 1 1 Las bombas para sumidero est n dise adas para funcionar intermitentemente y habit...

Страница 15: ...na salida de corriente dedicada Luego conecte el enchufe macho est ndar de la bomba a la parte trasera lado hembra del enchufe de los interruptores en t ndem 4 6 Afiance los cables de alimentaci n a l...

Страница 16: ...as 4 Motor defectuoso 5 Bloqueo con aire 6 Baja tensi n 7 Carga del sistema demasiado alta 8 Bomba obstruida 9 Control de nivel defectuoso o interruptor situado incorrectamente 10 Direcci n incorrecta...

Страница 17: ...vertical 12 8 5 2 Sin interr Manual Manual 9 115 7 1 LSP07 10 1 20 1 Interr de 12 5 6 5 12 3 8 15 6 8 230 3 5 ngulo ancho SP024 2 4 1 SP025 10 1 Interr vertical 10 6 3 9 3 8 SP035 1 3 115 3 0 1 8 3 6...

Страница 18: ...l sumidero Figura 3 ENCHUFE EL CTRICO DE LA BOMBA V LVULA DE RETENCI N ENCHUFE DE INTERR EN T NDEM RECEPT CULO DE PARED CONECTADO A TIERRA INTERRUPTOR DE FLOTADOR UNI N ORIFI CIO DE ALIVIO DE 1 8 PULG...

Страница 19: ...emergentes de cualquier naturaleza y e el reembolso de cualquier p rdida causada por la interrupci n del servicio A los fines de esta garant a los t rminos Distribuidor Comerciante y Cliente se define...

Страница 20: ...T Goulds Pumps Pompes de puisard Manuel d installation et d utilisation Goulds Pumps est une marque d ITT Water Technology Inc une filiale d ITT Industries Inc www goulds com Engineered for life Eaux...

Страница 21: ...cien qualifi Il faut toujours suivre les pres criptions du code provincial ou national de l lectricit On doit brancher la pompe un circuit lectrique ind pendant prot g par un disjoncteur ou des fusibl...

Страница 22: ...es d arr t saisonni res Mod le ST est art de l auto portrait venting aucun trou n est exig 3 TUYAUTERIE 1 INFORMATIONS G N RALES 1 1 Les pompes de puisard sont con ues pour un usage intermittent g n r...

Страница 23: ...le courant au panneau de disjonc teurs ou au sectionneur ou aux deux si c est le cas 5 2 Remplir le puisard ou la cuve d eau et noter le niveau de l eau quand la pompe d marrage et arr te La pompe de...

Страница 24: ...ans ARR T DE LA POMPE V causes probables 7 8 9 10 et 13 R P TITION SANS ARR T DU CYCLE DE FONCTIONNEMENT V causes probables 9 11 12 et 13 CAUSES PROBABLES 1 Protecteur thermique d clench 2 Disjoncteur...

Страница 25: ...LSP07 10 1 d placem 20 1 angul 12 5 6 5 12 3 8 15 6 8 230 3 5 SP024 2 4 1 SP025 10 1 Vertical 10 6 3 9 3 8 SP035 1 3 115 3 0 1 8 3 6 Aucun contacteur Manuel Manuel SP28C 115 75 W 10 1 Autocommande pa...

Страница 26: ...HE DE LA POMPE CLAPET DE NON RETOUR FICHE PRISE DU CONTACTEUR PRISE MURALE MISE LA TERRE RACCORD UNION TROU PUR GEUR D AIR DE 1 8 po PLAGE DE POMPAGE DONN ES SUR L INSTALLATION DONN ES SUR L INSTALLAT...

Страница 27: ...23 NOTES NOTAS NOTES NOTAS...

Страница 28: ...les pertes d coulant de la panne Aux fins de la pr sente garantie les termes ci dessous sont d finis comme suit 1 Distributeur signifie une personne une soci t de personnes une soci t de capitaux une...

Отзывы: