Alarm source
Action
FLS10
1. Drain the fluid in the inspection chamber. Fill with new
coolant if necessary.
2. Check the freezing point (lower than -13°C or 9°F).
Check the inspection chamber again after one week of operation. If
leakage has occurred:
1. Drain the fluid.
2. Change the mechanical seal unit.
3. Replace with new coolant.
The thermistor/Thermal contact 1. Check the coolant level.
2. Check the start and stop levels.
The overload protection
Check that the impeller can rotate freely.
Maintenance (Continued)
Flygt 5150.350, 5150.360 Installation, Operation, and Maintenance Manual
39