Section 11, Maintenance
11- 4 Installation Manual for Hurricane® Zephyr™ HW
Heating System
MAINTENANCE ITEM
MAINTENANCE
FREQUENCY
SERVICE REQUIRED
Air/FUEL/WATER HOSES
SEASONALLY
INSPECT FOR LEAKS AND
WEAK POINTS
HOSE CLAMPS
SEASONALLY
INSPECT FOR CORROSION
TIGHTEN IF LOOSE
COMBUSTION CHAMBER
AND EXHAUST
1000 HOURS
VACUUM CLEAN
FUEL FILTER
SEASONALLY
INSPECT FOR CLEANING
OR REPLACEMENT
NOZZLES
DISTRIBUTOR ORIFICE,
AIR SLOTS & O-RINGS
SEASONALLY OR
2000 HOURS
CLEANING AND
INSPECTION FOR WEAR
AND DAMAGE
EXHAUST SYSTEM
SEASONALLY
INSPECT FOR LEAKS AND
CORROSION
COOLANT MIXTURE
36 MONTHS
11 MONTHS
REPLACE
Ph LEVEL FOR ACIDITY
ELECTRONIC CONTROL
PANEL
SEASONALLY
VOLTAGE TEST / INSPECT
FOR CORRODED WIRES
AIR COMPRESSOR
FUEL PUMP
COMBUSTION FAN
MOTOR
SEASONALLY
INSPECT FOR LEAKS,
CORROSION & WEAR
Figure 11-1 Maintenance Schedule
11.9 Protecting Hydronic Heating Systems
The advantage of closed hydronic heating systems is that as long
as there are no leaks, (i.e., no need for constant make-up
water), the fill neutralizes (that is, it reaches equilibrium). The
long-term result is minimal scale build-up and insignificant
corrosion since after operating for a period of time, most oxygen
has been "starved" out of the boiler fill water. While boiler fill
water treatments have their place, leak prevention is the single
most important preventative maintenance item.
Regular maintenance and prompt repair of leaks, combined with
a one-time application of appropriate inhibitors, can help you
enjoy problem-free heating. Since it is difficult to guarantee that
a hydronic heating system will never leak, corrosion inhibitors
Содержание Hurricane Zephyr HW
Страница 14: ...Section 1 Overview 1 8 Installation Manual for Hurricane Zephyr HW Heating System...
Страница 20: ...Section 2 Mounting the Heater Unit 2 6 Installation Manual for Hurricane Zephyr HW Heating...
Страница 28: ...Section 4 Installing the Fuel System 4 4 Installation Manual for Hurricane Zephyr HW Heating System...
Страница 34: ...Section 5 Installing Fan Heaters 5 6 Installation Manual for Hurricane Zephyr HW Heating System...
Страница 43: ...Section 6 Wiring the Electrical System International Thermal Research 6 9...
Страница 83: ...Section 11 Maintenance 11 6 Installation Manual for Hurricane Zephyr HW Heating System...
Страница 88: ...International Thermal Research Warranty Information International Thermal Research Page 5...
Страница 89: ...Warranty Information International Thermal Research Page 6 International Thermal Research...