Green Heating Technology
21
Flue systems
Intake/outlet flange
The boiler is equipped with a flange for connecting inlet and
outlet flues pipes; this flange has been studied for collecting
rain/water that may creep into the inlet pipe and for avoid-
ing that rain reaches the burner’s fan.
Rain/water collected is conveyed, thanks to silicon tube, to
internal siphon for draining
On the flange there are:
f
outlet pipe connection
1
, both coaxial and separate configurations;
f
inlet for coaxial configuration
2
;
f
inlet pipe connection for separate configuration
3
(remove the cap only if you are installing the
separate configuration);
f
prearrangement
4
for an accessory not provided with this model (to be NOT opened).
Pay attention to only connect
inlet separate
pipe to
connection 3
,
instead of prearrangement
4
�
This wrong connection could allow rain/water going to fan and burner, damaging it.
Installation of the flue intake/outlet flange gasket
IMPORTANT:
For a correct and safe op-
eration of the boiler it’s necessary to
install, on the intake/outlet flange
2
, the
gasket
1
included in the boiler’s docu
-
ments bag. Before inserting the flue out
-
let pipe it’s therefore very important to
correctly place the gasket on its seating
as indicated in the figure.
General indications
To grant the functionality and efficiency of the
appliance it is indispensable to realize intake and
outlet ducts using flue accessories specific for
condensing boilers�
WARNING: the specific flue accessories components for condensing boilers, especially the parts
which are in touch with the flues outlet, are so projected because they are made with
plastic
materials acids resistant
, but because of their nature,
they are not suitable to resist to the
higher temperature
of the flues of the traditional boilers. So
it is not possible to use traditional
flue components for the outlet ducts of the condensing boilers, neither vice versa.
When installing the pipes, we recommend lubricating the inside of their gaskets exclusively with
silicone
lubricants since their material (EPDM peroxide) is not compatible with other types of
oils or greases
intake for
split system
DON'T
use!