background image

 

 

Operation of the Unit: 

With the panel service switch ON, engage the Key-switch.  The circuit will activate and the panel Green LED will 
illuminate to indicate that the water services to the testing restroom are active.  After turning a switch OFF, it will be 
necessary to re-engage the Key-switch in order to reactivate the services.  The Red LED will illuminate when the 
circuit is OFF. 
 
Pressing the panic button will deactivate the services.  All Panel lights should illuminate with Panic. 
 
Once in the Panic Mode the Key-switch must be engaged in order to reactivate service.  The Alarm Signal must be 
withdrawn prior to reactivation. 
 
This unit utilizes latching solenoids that pulse ON with circuit active to open the water supply and pulse OFF with 
circuit inactive to close it.  Where provided, secondary solenoid(s) are provided that pulse ON when inactive in 
order to provide drain-down of supply piping. 

 

 
Equipment Maintenance: 

 

The DLA Series Controller should have semi-annual inspections.

 

 

ISIMET 

recommends that you periodically conduct a brief test of the system to verify that the output circuit 

performs as intended.

 

 

If examination of the unit indicates tampering, 

ISIMET 

recommends that you first review the installation and 

wiring portions of this manual prior to placing the unit in service.

 

 

ISIMET

 recommends that piping systems be thoroughly flushed and cleaned and tested for leaks prior to 

placing the system into use.  Periodic testing of these solenoids will assure that the piping system continues to 
function properly.

 

 

If you have any questions regarding the operation and maintenance of the DLA Controller, please contact an 

ISIMET 

Service Representative. 

 
The enclosure has a NEMA 1 rating.  It is not intended for use in wet areas.  Exercise caution to prevent exposure of 
the interior compartment of the enclosure to moisture.  If moisture is present within the enclosure, 

ISIMET

 

recommends that the control switch be turned OFF, power be disconnected from the unit until the source of the 
moisture is determined, and all moisture is removed from the compartment. 
 
The electronic controller (PCB) is sensitive to dust and other air-borne particles.  Do not expose the interior 
compartment of the enclosure to dust.  During the semi-annual inspection, if dust or other material is present, 

ISIMET 

recommends that you remove all foreign matter before operating the unit. 

 
If the Unit fails to operate, 

ISIMET

 recommends that you check the power supply to the unit.  With the control 

switch in the ON position, LED Fuse 1 should illuminate.   If not, check the service breaker and PCB fuses. 
 
If the fuse is not damaged and the unit still does not function, contact ISIMET or your local Service Representative.   

 
 

 

 

 
 
 
 
 
 
 
 
 
 

CAUTION: 
ISIMET DOES NOT recommend that service to emergency and/or safety devices, such as emergency 
showers and eyewashes, be controlled by the DLA Controller System or Solenoids.  Such devices are 
intended to operate independent of restrictive authority operation, as is the case with the design of this unit.  
ISIMET makes available components for the monitoring of such safety devices.  Please contact ISIMET 
regarding any questions regarding this type of application. 

Содержание DLA Series Style 2

Страница 1: ...esting Labs Style 2 W Ver 4 41 pcb Pulse Relay pcb s Installation Operations Start up and Maintenance Instructions Table of Contents Page Warranty 2 Enclosure Specifications and Dimensions 3 Styles 3...

Страница 2: ...period of two years from date of installation when installation complies with all start up and routine maintenance procedures and Start up has been performed by an authorized factory representative R...

Страница 3: ...owder coated sheet metal 6 0 X 14 25 X 4 0 all dimensions are in inches Style Output Circuits Trans former Switch Breaker pcb Fuse 1 Output Rating standard Pulse Output DLA 2 1 24 vac 2 amp 5 amp 2 am...

Страница 4: ...ening From within the cabinet fit into opening and fasten unit to back of casework Face of wall box should be even with face of cabinet After mounting unit protect interior of box from construction de...

Страница 5: ...valves Connect both supply valves to pins 4 5 or Utilize when one 1 supply and one 1 drain down solenoid is provided Connect supply valve to pins 4 5 Connect drain down to pins 6 7 Figure 2 Utilized...

Страница 6: ...n counter clockwise the two retaining clips at the top of the Panel and open Insert plug onto circuit header on PCB Turn Power ON Close the panel and lock CAUTION Do not install the panel until all wa...

Страница 7: ...he piping system continues to function properly If you have any questions regarding the operation and maintenance of the DLA Controller please contact an ISIMET Service Representative The enclosure ha...

Страница 8: ...logy ISIMET believes that sole and local authority means that the primary operator or the instructors should have the sole authority to start and stop the utility services within the immediate area of...

Отзывы: