WARNING!! Other pcb Jumper placements
Jumpers at JP 1, JP 4 and JP 5 are factory placed in order to configure the circuit board to specific functions for the
Controller. Removal and/or re-placement may cause the unit to malfunction.
Figure 1:
Utilized when two (2) supply solenoids
are provided without drain-down valves.
Connect both supply valves to pins 4 & 5.
or
Utilize when one (1) supply and one (1)
drain-down solenoid is provided.
Connect supply valve to pins 4 & 5.
Connect drain-down to pins 6 & 7.
Figure 2:
Utilized when two (2) supply solenoids are
provided with two (2) drain-down valves.
Connect both supply valves to pins 4 & 5.
And both drain-down valves to pins 6 & 7.
Monitoring Circuit- JP3
Output Configuration Jumpers
@ Panic Output
1 jumper across center two posts
= dry-contact.
2 jumpers across each pair of posts
= 24-vac output