isel
- CAN - I/O
– Modules: Operating Instruction
Page - 6
CAN
– I/O - 16/16
digital inputs:
16
In1.1 to In1.8 and In2.1 to In2.8
using optocouplers (input current about 8mA)
digital outputs:
16
Out1.1 to Out1.8 and Out2.1 to Out2.8
8 relay outputs Out1.1 to Out1.8, Imax < 5A
8 electronic outputs (switching transistors)
Out2.1 to Out2.8, Imax < 350mA,
switching delay about 100µs,
thermic protection,
short-circuit protection
catch diode for digital
outputs
Each inductive load plugged to digital outputs requires
a separate external catch diode.
analog output:
1
0V
– 10V over 8 Bit D/A converter
(if the analog output is used the eight electronic digital outputs Out2.1 to Out2.8
can not be used for binary output)
fuse:
630 mA / 250V fast
CAN
– I/O - 8/12 - 4/1
digital inputs:
8
In1.1 to In1.8
using optocouplers (input current about 8mA)
digital outputs:
12
Out1.1 to Out1.8 and Out2.1 to Out2.4
4 relays outputs Out2.1 to Out2.4, Imax < 5A
8 electronic outputs (switching transistors)
Out1.1 to Out1.8, Imax < 350mA,
switching delay about 100µs,
thermic protection,
short-circuit protection
catch diode for digital
outputs
Each inductive load plugged to digital outputs requires
a separate external catch diode.
analog output:
1
0V
– 10V over 8Bit D/A transformer
analog inputs:
4
Ana In1 bis Ana In4, 0V
– 10V, 16 Bit resolution
fuse:
630mA / 250V fast