1.4 Functional description
The simplified functionality of the device is described below.
Next to the mains there is a EMI/RFI filter, which feeds the power factor correction unit (PFC) and the inrush current limitation
circuit. The PFC draws sinusoidal currents from the mains, which are in phase with the supply voltage.
INFORMATION
INFORMATION
With an input voltage greater than 255 V, the PFC only functions as a rectifier and the current consumption is
no longer sinusoidal. In the input voltage range below 100 V, either the output power or the ambient
temperature must be reduced (see Figure 13: Power reduction vs. input voltage: Power reduction as a function
of the input voltage).
Furthermore the PFC provides a DC link voltage, that is buffered by electrolytic capacitors. An inverter with a connected
resonance circuit transforms the DC-Link voltage into a controllable sinusoidal voltage. The HV transformer and HV rectifier
provide an output voltage corresponding to the external set voltage. Output voltage and current are measured by high precision
voltage dividers and a shunt and are fed back to the control circuit. A damping resistor connected to the output capacitance
limits the output current during a load change or ARC.
High voltage power supplies of this class work with a fixed switching frequency. The output parameters are controlled via a pulse
width modulation (PWM).
The control circuit controls and limits the output voltage and current corresponding to the set values. Normalized monitor
voltages for voltage and current are provided for read back. The control circuit is also monitoring the input voltages, auxiliary
voltages and the temperatures of cooling air and single components.
The power supply is turned ON/OFF with a switch installed at the front panel of the power supply (applies to device classes 300W
and 800W).
Optionally, the device is equipped with an ARC management.
Optionally, the device can be supplied as a capacitor charger (CLD - very low overshoot of the output voltage).