Engineering
18
218150 / 948260310020
2015-12-16·BA00·III·en·01
Temperature Input Module Zone 2
Series 9482/33
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
Type of circuitry E: TC with ext. CJC, grounded
16558E00
Up to 8 earthed thermocouples or mV transmitters with external reference junction
NOTE
The following safety data are only applicable to earthed thermocouples and mV
transmitters with external reference junction. The safety data for the thermocouples and
external reference junction must be determined separately. If one or several resistance
sensors are to be connected to the module, see type of circuitry G or I. Thermoelements
and mV transmitters can be connected in any constellation. The external reference
junction may only be connected to channels 6 and 7.
Installation type
earthed
Reference junction
external
Max.
output voltage Uo ext
12.92 V
Max. current Io
25.0 mA
Max. power Po
81.0 mW
Max. input voltage Ui
6.5 V
Note
max. input voltage Ui is the sum of all inputs
Max. connectable
Inductance Lo /
capacity Co
IIC
IIB / IIIC
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
T
mV
mV
mV
mV
Lo [mH]
72
50
10
2
1
0.5
0.2
Co [
m
F]
0.17
0.22
0.34
0.46
0.53
0.62
0.78
Lo [mH]
100
20
5
1
0.5
0.2
0.1
Co [
m
F]
1.2
1.6
2.1
3.0
3.5
4.5
5.7