Temperature Input Module Zone 2
Series 9482/33
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
Insulated external reference junction
Installation type
insulated
Reference junction
external (3-wire)
Max.
output voltage Uo ext
12.92 V
Max. current Io
17.4 mA
Max. power Po
56.2 mW
Max. input voltage Ui
6.5 V
Note
max. input voltage Ui is the sum of all inputs
Max. connectable
Inductance Lo /
capacity Co
IIC
IIB / IIIC
Lo [mH]
66
50
20
5
1
0.5
0.2
Co [
m
F]
0.17
0.21
0.29
0.39
0.53
0.62
0.78
Lo [mH]
100
20
5
1
0.5
0.2
0.1
Co [
m
F]
1.2
1.6
2.1
2.9
3.5
4.5