Engineering
16
218150 / 948260310020
2015-12-16·BA00·III·en·01
Temperature Input Module Zone 2
Series 9482/33
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
EN
Type of circuitry D: TC with ext. CJC, ungrounded
16496E00
Up to 8 insulated thermocouples or mV transmitters with external reference junction
NOTE
The following safety data are only applicable to the wiring of insulated thermocouples
and mV transmitters with external reference junction. The safety data for the
thermocouples and external reference junction must be determined separately. If one or
several resistance sensors are to be connected to the module, see type of circuitry F or
H. Thermoelements and mV transmitters can be connected in any constellation.
The external reference junction may only be connected to channels 6 and 7.
Installation type
insulated
Reference junction
external
Max.
output voltage Uo ext
12.92 V
Max. current Io
6.53 mA
Max. power Po
21.1 mW
Max. input voltage Ui
6.5 V
Note
max. input voltage Ui is the sum of all inputs
Max. connectable
Inductance Lo /
capacity Co
IIC
IIB / IIIC
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
T
mV
mV
mV
mV
Lo [mH]
100
50
10
5
1
0.5
0.2
Co [
m
F]
0.30
0.32
0.38
0.42
0.55
0.63
0.79
Lo [mH]
100
50
10
1
0.5
0.2
0.1
Co [
m
F]
1.5
1.6
1.9
3.0
3.5
4.6
5.7