7
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Planning Installation
Safety and General
Installation
Operation
Maintenance
Troubleshooting
Parts / Accessories
Bottom
Clearance
Thermal Protection
Thickness
Hearth Extension Depth
USA
Canada
0" (0mm)
2-1/2" (64mm)
18” (450mm)
18” (450mm)
8" (203mm)
0” (0mm)
18” (450mm)
18” (450mm)
Table 6 - Hearth Extension / Thermal Protection Requirements
Montlake™ 300
ZC Fireplace
UL 127
Masonry Fireplace
UBC Chapter 37
G
Depth Min.
16-1/2” (419mm)
16-1/2” (419mm)
H
Height Min.
23-1/2” (597mm)
23-1/2” (597mm)
J
Lintel Max. Depth
u
5-3/8” (137mm)
5-3/8” (137mm)
K
Front Width Min.
36” (914mm)
29-1/2” (749mm)
L
Rear Width Min.
26-1/4” (667mm)
27-1/4” (692mm)
u
Without use of adjustable offset box or smoke deflector
Table 5 - Fireplace Sizing
Figure 7 - Minimum Fireplace Cavity
Also see appliance dimensional views on
Page 9
(see
Figure 9
).
*Distance between hearth and the bottom of the appliance
G
H
K
L
Model
F (1)
G
H
J(2)
M
ML300
USA-18”
CAN-450mm
USA-15”
CAN-381mm
22-5/8”
575mm
5-3/8”
137mm
USA-48-3/4”
CAN-1238mm
Table 4 - Clearances
* Reduced clearances may be available for A, B, C and D dimensions per
NFPA 211 - latest edition, Standard for Chimneys, Fireplaces, Vents and
Solid Fuel-Burning Appliances (in Canada CSA B365 - latest edition). See
section on “Reduction of Appliance Clearance with Specified Forms of
Protection.”
(1) (USA) 18” minimum hearth extension on all stoves and inserts as measured
from the door opening of the unit. (Canada) 18”(450 mm) minimum hearth
extension on all stoves and inserts as measured from the door opening of
the unit. Minimum distance of floor protection to the side = 8” (200 mm).
This is measured from the sides of the door opening in the USA and from
the sides of the insert in Canada.
(2) J = Maximum lintel depth without flue offset or smoke deflector.
NOTES:
• Facing material that projects more than 3/4” (19 mm) from the wall
is considered a mantel or side wall.
Model
A*
B*
C *
D*
E(1)
ML300
USA-26”
CAN-660mm
USA-24”
CAN-610mm
8”
203mm
8”
203mm
USA-8”
CAN-203mm
WARNING: BE ABSOLUTELY SURE THE DISTANCE BETWEEN THE
HEATER AND THE SURFACE OF ANY COMBUSTIBLE CONSTRUC-
TION IS NOT LESS THAN SHOWN ON THIS PAGE.
Figure 5
Figure 6
Maximum Mantel Depth = 10” (254mm)
COMBUSTIBLE MANTEL
Top Facing / Trim
Side Facing Material
SIDE W
ALL
C
Insert
D
B
A
E (USA)
E (Canada)
Hearth Protection
6” Ø
Flue Collar
Mantel
Trim
M
F
G
J
H
10-5/8”
270mm
Hearth Protection
Montlake™ ML300
REqUIRED CLEARANCES
Planning Installation