Vertical Venting 

(see Figure 5, Page 15)

The vent pipes must be connected to the proper collars on the unit and 

the exhaust vent pipe must be connected to the termination cap or the unit 

will not operate. When done assure all connections are securely fastened.

The fireplace and fireplace chimney must be clean and in good working 

order and constructed of non-combustible materials. Inspect chimney 

cleanouts for proper fit and seal.

Make sure that both liners will pass through existing damper area. 

Remove or lock damper to allow the passage of the flexible liners. If 

the damper will not allow the passage of both liners, DO NOT PROCEED 

FURTHER.  (If fireplace is masonry) Consult a local mason for removal 

of the damper without risk of structural damage or leakage (if the fire-

place is factory built) The appliance may NOT be installed into the fireplace.

        

WARNING

Direct-Vent Fireplace Insert Vent Requirements - Use liner 

listed to UL181 (Factory-made Air Ducts And Air Connec-

tors) or UL1777 (Chimney Liners) for the AIR INTAKE.  Use 

liner listed to UL1777 ONLY for the EXHAUST.
Do not substitute the heat-rated flex liner (UL1777) for 

the exhaust with any other type liner or a fire may result 

causing property damage, personal injury or loss of life.

Zero Clearance Fireplace Installation

This appliance may be installed in a masonry or factory built/zero clear-

ance (ZC) fireplace. When installing in a ZC fireplace, the ZC grate must 

be removed and the ZC damper must be removed or secured open. The 

ZC doors, screen, refractory or masonry lining, baffles and smoke shelf 

may be removed if necessary to install the gas insert. However, do not cut 

or alter the fireplace components. The removal of any parts to facilitate 

installation must not alter the integrity of the inner or outer shells of the 

fireplace cabinet. Any parts removed must be replaceable if the insert is 

taken out of the fireplace or the fireplace clearly marked with a paint stick 

that "This fireplace has been altered and is no longer safe to operate." 

If the factory-built fireplace has no gas access hole(s) provided, an access 

hole of 1.5" (38.1 mm) or less may be drilled through the lower sides or 

bottom of the firebox in a proper workmanship like manner. This access 

hole must be plugged with a non-combustible insulation after the gas 

supply line has been installed.

Si le foyer préfabriqué ne comporte pas d’orifices d’amenée du gaz, 

un orifice d’au plus 38,1 mm (1,5 po) peut être pratiqué, selon les 

règles de l’art, dans la partie inférieure des parois ou au fond de 

la chambre de combustion. Cet orifice doit être obturé au moyen 

d’isolant incombustible une fois la conduite de gaz en place.

The installer must mechanically attach the marking supplied with the gas 

fireplace insert to the inside of the firebox of the fireplace into which the 

gas fireplace insert is installed. See Figure 1 on Page 11.

Figure 7   

Flue Restrictor 

The flue restrictor settings shown in 

Figure 7

  a

re for typical installations 

and are based upon laboratory testing.  To achieve proper combustion, 

adjustments may be needed to account for variables in the installation, 

elevation, and typical operating temperatures.

Allow the appliance to burn for at least 10 minutes before determining 

proper flame appearance.  If the proper flame appearance cannot be 

achieved, the flue restrictor may need to be changed to a different posi-

tion. See the following guidelines to determine if you need to readjust 

the flue restrictor.

Flue Restrictor Adjustment

1.  Using a phillips screwdriver, remove the two screws holding the flue 

restrictor in place.

2.  Refer to table in Figure 7 and position the flue restrictor to the recom-

mended setting and reattach with the two screws removed in step 1.

Symptoms - Lack of Combustion Air

If the symptoms listed below are present, you may need to adjust the 

flue restrictor to a more open position.

•  Flame appears yellow

•  Floating Flames (lazy, ill defined, quiet, may roll)

• Sooting

•  Pilot becomes yellow and appliance shuts down

Symptoms - Excessive Combustion Air

If the symptoms listed below are present, you may need to adjust the 

flue restrictor to a more closed position.

•  Low Flame

•  Pilot pulls and appliance shuts down

•  Pilot flame ghosts

Model

Venting Height

Position

Natural Gas (NG)

BV32

25' or less

#1 (factory setting)

25' & up

# 2

BV27

20' or less

# 2

20' & up

# 2

Propane (LP)

BV32

10' - 15'

# 0

15' - 25'

#1 (factory setting)

25' & up

# 2

BV27

10' - 15'

# 0

15' - 25'

# 0

NOTE: Setting 0 is open, and setting 3 is closed.

3      

2 1

0

4

Содержание BELLEVUE 27

Страница 1: ...gas supplier call the fire department Installation and service must be performed by a quali fied installer service agency or the gas supplier WARNING FIRE OR EXPLOSION HAZARD Failure to follow safety...

Страница 2: ...VIDRIO CALIENTE LOS NI OS DEBEN NUNCA TOCAR EL VIDRIO L cran pare tincelles fourni avec ce foyer r duit le risque de br lure en cas de contact accidentel avec la vitre chaude et doit tre install pour...

Страница 3: ...o Supervise en forma cercana a los ni os en cualquier cuarto donde haya una chimenea funcionando para impedir el contacto con el vidrio Mantenga la ropa mobiliario gasolina y otros l quidos inflamable...

Страница 4: ...eatures 12 Packaging List 12 Ratings 12 Insert and Fireplace Dimensions 13 Clearances to Combustibles 14 Insert Leveling 14 Installation 15 21 Venting Installation 15 USING THIS MANUAL Please read and...

Страница 5: ...ls viennent en contact avec la surface chaude Il est recommand d installer une barri re physique si des personnes risques habitent la maison Pour emp cher l acc s un foyer ou un po le installez une ba...

Страница 6: ...r liminerlapoussi re et les traces de graisse ou d huile Collez l tiquette sur la surface de la plaque du r cepteur mural qui contr le le foyer Figure A Choisissez la langue qui est principalement par...

Страница 7: ...Collezl tiquettesurlebo tier de la t l commande Figure B Choisissez la langue qui est principalement parl e dans la r sidence du propri taire En cas de doute collez l tiquette en anglais 3 Si vous ne...

Страница 8: ...anemia those under the influence of alcohol and those at high altitudes Turn off gas and electrical power to the appliance and allow it to cool before cleaning or servicing the appliance If the barri...

Страница 9: ...dition and will void the warranty Please carefully read the sections pertaining to these subjects and or be sure your appliance is properly equipped Never use solid fuels such as wood paper cardboard...

Страница 10: ...l wood burning fireplace listed to UL 127 or ULC S610 only All exhaust gases must be vented outside the structure Combustion air is drawn from outside the structure When installing in a factory built...

Страница 11: ...een tested and certified to ANSI Z21 88 CSA 2 33 Standard for Vented Gas Fireplace Heater and CAN CGA 2 17 M91 and UL 307B Gas Burning Heating Appliances for Manufactured Mobile Homes in both USA and...

Страница 12: ...a specified elevation Only IHP conversion kits can be used to convert from NG to LP or LP to NG Contact your IHP dealer for details PRE INSTALLATION RATINGS Bellevue 27 Bellevue 32 NATURAL GAS LP GAS...

Страница 13: ...Dim Description Bellevue 27 Bellevue 32 A Front Opening Width 27 686mm 32 813mm B Height 18 457mm 19 1 2 495mm C Rear Width 17 432mm 22 559mm D Fireplace Depth 15 381mm 16 406mm Model A B C D E F G H...

Страница 14: ...and the minimum projection of the hearth extension Figure 4 Bellevue 27 32 Clearances MINIMUM CLEARANCES MINIMUM CLEARANCES TO COMBUSTIBLES Bellevue 27 32 A Mantel 32 813mm B Side Wall 4 102mm C Mante...

Страница 15: ...hould be used for correct operation Liner Requirements Use 3 77 mm diameter listed gas vent liner UL1777 ONLY for the EXHAUST Use 3 77 mm diameter listed liner UL 181 or UL1777 for the AIR INTAKE Figu...

Страница 16: ...mm or less may be drilled through the lower sides or bottom of the firebox in a proper workmanship like manner This access hole must be plugged with a non combustible insulation after the gas supply l...

Страница 17: ...the openings on the side mounting brackets on the appliance see Figure 9 Figure 9 A Openings where hooked brackets on Full Front Facade will hang B Side Mounting Brackets on appliance A A B B A A Inst...

Страница 18: ...ure 11 4 Position the separated glowing embers over the small holes on the burner surface Figure 12 Do NOT cover the large burner slots NOTE Enough glowing ember material is provided for several appli...

Страница 19: ...14B Place embers and other media see Page 18 Figure 14A Locate the log placement tabs BV27 Figure 14B Locate the log placement tabs BV32 Figure 15 Place log 1 4 Position the left front log 2 on the le...

Страница 20: ...ave step down regulators to reduce the pressure to safe levels Check the taps for gas leaks with a gas leak test solution retighten if necessary LP and Natural Gas Supplies This appliance is equipped...

Страница 21: ...the adjustment lever side to side see Figure 20 CAUTION The air shutter should never be set so as to make the tips of the flames sooty or create sooting on the viewing glass logs or heat exchanger If...

Страница 22: ...o intermittent mode Tohaveastandingpilotwhichwillhelpstartupduringcoldclimate conditions by warming the flue and the glass switch to standing pilot The standing pilot mode is indicated by a pilot that...

Страница 23: ...cessivetimesfortenminutes each time with a five minute cool down between each firing Ventilate the house during these first firings as the paint gives off an unpleasant odor It is recommended that per...

Страница 24: ...odule Inlet Inlet To Pilot Igniter From Pilot Thermocouple 7 5VDC 1 Amp Adaptor Burner On Off brown Hi Lo blue IPI Cont Pilot yellow Learn black Thermocouple To S Terminal on Main Module Battery Motor...

Страница 25: ...e o Checkthatthechimneyanditsoutletareopenandfreeofsoot block age or debris The venting system should be periodically examined by a qualified agency o Check gaskets once a year Gaskets must be tight R...

Страница 26: ...verse order WARNING Do not attempt to substitute the materials used on these doors or replace cracked or broken glass Handle this glass with extreme care Glass is susceptibletodamage Donotscratchorhan...

Страница 27: ...latest edition or the Canadian Electrical Code Part 1 CSA C22 1 latest edition see Operating Options Figure 23 Page 22 Blower Assembly Fireplace Insert Back Repair If the glass is broken in the glass...

Страница 28: ...ks from the mounting slots on the unit 3 Place the Full Front Facade face down on a soft non abrasive surface to prevent damage 4 Remove barrier from Full Front Facade a Using a 3 8 nut driver remove...

Страница 29: ...TLET VENTS See Firebox Liner Kit and Log Set Installation on Pages 17 19 The main Burner comes on but then goes out Gas is not reaching the appliance Loose wires to the valve or ignition module Pilot...

Страница 30: ...ow RF Control Module F2694 50 Rocker Switch IPI CPI Hi Lo Burner On Off F3182 51 Rocker Switch Momentary Learn F2964 Item Description Cat No 1 Firebox Door Assembly with Glass H9174 2 Gas Train Assemb...

Страница 31: ...31 NOTE DIAGRAMS ILLUSTRATIONS ARE NOT TO SCALE REPLACEMENT PARTS BELLEVUE 27 50 51 18 10 11 14 14 5 8 9 19 20 1 15 6 7 21 16 17 28 41 49 13 40 25 43 32 2...

Страница 32: ...4 14 Full Front Facade Mounting Bracket Kit set of two H9178 15 Refractory Panel Retaining Bracket Kit two sets one of each style J7596 16 90 Elbow Brass 3 8 Tube x 3 8 NPT J7701 17 Battery Holder J79...

Страница 33: ...33 NOTE DIAGRAMS ILLUSTRATIONS ARE NOT TO SCALE REPLACEMENT PARTS BELLEVUE 32 2 50 51 52 40 25 13 49 43 41 16 17 28 10 11 1 5 6 7 8 9 14 15 21 19 14 20...

Страница 34: ...Surround Trimmable 46 W x 38 H Ecoflow Control Kits F2687 EF BRCK Basic Remote Control On Off IPI CPI F2660 EF WWRCK Wireless Wall Switch On Off High Low ON OFF HI LO ON OFF HI LO PILOT Continuous Ba...

Страница 35: ...coflow Control Kits F2687 EF BRCK Basic Remote Control On Off IPI CPI F2660 EF WWRCK Wireless Wall Switch On Off High Low ON OFF HI LO ON OFF HI LO PILOT Continuous Basic Remote Wireless Wall Switch D...

Страница 36: ...ELECTRICAL RATING 120 VAC 60 HZ LESS THAN 2 AMPS CHIMNEY USE 3 76 MM GAS VENT FLEX CHIMNEY LINER LISTED TO UL 1777 OR ULC S635 THIS APPLIANCE MUST BE PROPERLY CONNECTED TO A VENTING SYSTEM IN ACCORDAN...

Страница 37: ...610 M 38 101 53 0595 UNIT FACTORY EQUIPPED FOR 0 2000 FT 0 610 M IN CANADA 0 4500 FT 0 1370 M ELECTRICAL RATING 120 VAC 60 HZ LESS THAN 2 AMPS CHIMNEY USE 3 76 MM GAS VENT FLEX CHIMNEY LINER LISTED T...

Страница 38: ...t try to light the pilot by hand B BEFORE OPERATING smell all around the appliance area for gas Be sure to smell next to the floor because some gas is heavier than air and will settle on the floor WHA...

Страница 39: ...cause damage to the Product will produce excessive temperatures and could result in a fire hazard c damages caused by failing to provide proper maintenance and service in accordance with the instruct...

Страница 40: ...ur IHP distributor or dealer Parts will be shipped at prevailing prices at time of order When ordering repair parts always give the following information 1 The model number of the appliance 2 The seri...

Отзывы: