
14
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
CLEARANCES TO COMBUSTIBLES
Minimum Clearances to Combustibles
Minimum clearances include any projections such as shelves, window
sills, mantels, spacers/standoffs or surfaces to combustible construction
etc. above the appliance. Paint or lacquer used to finish the mantel
must be heat resistant in order to avoid discoloration.
Facing and Mantel Clearances
(see Figure 4)
The letters in Figure 4 (A through E) show minimum clearances required
from the appliance to combustibles and the minimum projection of the
hearth extension.
Figure 4 - Bellevue™ 27 & 32 Clearances
MINIMUM CLEARANCES
MINIMUM CLEARANCES TO COMBUSTIBLES Bellevue™ 27 & 32
A = Mantel .................................................. 32" (813mm)
B = Side Wall .................................................. 4" (102mm)
C = Mantel Depth ........................................... 10" (254mm)
HEARTH PROTECTION
D = Vertical Distance from base of appliance
0"
4"
to Hearth Extension ................................. (0mm) (
102
mm)
E = Minimum Horizontal Distance
10" 0”
from Front of Appliance........................... (254mm) (0mm)
Insert Leveling
At each front and rear corner of the insert is an adjustable leg provided
to level the insert should the hearth of the fireplace be uneven. To adjust
the legs, use a 1/4" wrench.
Non-Combustible
A
D
B
E
Mantel
C
Mantel
NOTE: Hearth protection to be min. 1/2” (13mm) thick
non-combustible or equivalent, with a k factor of .84.