Section IV
Maintenance
Page 4.10
BP
II S, 3.00
08/96
BATTERY A4
TO CB3–CC
BATTERY A3
BATTERY A2
BATTERY A1
TO CB3–BB
RED
BLK
Figure 4–1.
4.6.6
Reactivating the Batteries
0.
1. After all battery trays and their batteries
are in place and reconnected, verify the
UPS rectifier DC link voltage is at proper
value: 195 VDC minimum.
2. Replace top and left side panels.
3. Close the Battery Circuit Breaker only if
the link voltage is correct.