![Iom SYSCOIL 2 Скачать руководство пользователя страница 7](http://html.mh-extra.com/html/iom/syscoil-2/syscoil-2_installation-and-maintenance-manual_2086561007.webp)
English
Avoid contact with the coil surfaces and their sharp edges as they can be dangerous.
Caution
5
SysCoil 2
Size
SC10
SC20
SC30
SC40
SC50
SC60
SC70
SC80
Power supply
V
230V-50Hz / 230V-60Hz
Fan motor AC power
W
36
35
81
59
86
112
161
188
Power supply
V
230V-50Hz / 230V-60Hz
Fan motor EC power
W
41
42
45
43
46
53
77
108
Fuse rating Am
A
2
2
2
2
2
2
2
2
Fuse rating ASE / VDE
A
2
2
2
2
2
2
2
2
Cable section mini
mm²
3G1.5
3G1.5
3G1.5
3G1.5
3G1.5
3G1.5
3G1.5
3G1.5
IMPORTANT
These datas are given for guidance only. They must be checked aat commissioning according to prevailing
standards. They depend on the installation and the cables used.
A main fuse must mandatorily be provided on the power supply.
²
Fuses not supplied
²
Cables not supplied
5.2. ELECTRICAL SPECIFICATIONS
5.2.1. WITHOUT ELECTRIC HEATING
5.2.2. WITH ELECTRIC HEATING
Size
Electric heating capacity Fuse rating Gg
Fuse rating ASE / VDE Cable section mini
W
A
A
mm²
SC10
500
4
10
3G1.5
SC20
500
4
10
3G1.5
SC30
500
4
10
3G1.5
1000
4
10
3G1.5
SC40
1250
8
10
3G2.5
2500
16
16
3G2.5
SC50
1250
8
10
3G2.5
2500
16
16
3G2.5
SC60
1250
8
10
3G2.5
2500
16
16
3G2.5
SC70
1000
8
10
3G2.5
2000
16
16
3G2.5
SC80
1500
10
10
3G2.5
3000
16
16
3G2.5
SEE APPENDIX
6. DIMENSIONS
7. HANDLING
7.1. NET WEIGHT
Always take great care when handling the unit.
Do not lift the unit by its condensate outlet, by the water
connectors and by the mounting lugs
.
Size
SC10
SC20
SC30
SC40
SC50
SC60
SC70
SC80
VC / HC
2 pipes kg
18
18
21.5
27
30
35
35
50
4 pipes kg
19
19
22.5
29
32
37
37
52
VN / HN
2 pipes kg
12
12
14.5
20
22
26
27
41
4 pipes kg
13
13
15.5
22
24
28
29
43
Содержание SYSCOIL 2
Страница 2: ......
Страница 25: ...APPENDIX ANNEXE ANLAGE ALLEGATO ANEXO APPENDIX ANNEXE ANLAGE ALLEGATO ANEXO ...