After installing the unit, be sure that there is no more longitudinal and transversal counterslopes
avoiding condensate evacuation.
Caution
OK
11
SysCoil 2
9.4. CONDENSATE DRAIN LINE
For that, use a square and spirit level to make sure that fan coil unit is level and that it is at a 90 degree
DQJOHEHWZHHQWKHZDOODQGʿRRUVHHʿXRUHVFHQWVWLFNHURQXQLWFKDVVLV
1RWH,IWKHʿRRUDQGWKHZDOODUHQRWDWULJKWDQJOHLWPD\EHQHFHVVDU\WRVKLPWKHIDQFRLOXQLWWRLQVXUH
proper installation. Manufacturer will not accept any responsability on units not being on proper level.
The thermostat (change-over switch) supplied is
to be mounted on the water supply pipe.
The temperature sensor (change over)
VXSSOLHG LV WR EH ʾWWHG WR WKH ZDWHU LQOHW
tube.
Before assembling the change over sensor,
coat the tube with heat conducting paste
to guarantee that the real temperature is
recorded.
The 9 and 10 change over sensor inputs can
be connected to the mains power supply. If
it is necessary to extend the sensor wires,
ensure that wires appropriate for this voltage
are used.
Crimp the 6.35 F fast-on clips with their insulator
bushes (supplied) on the wires of this thermostat.
OPERATING TEMPERATURE RANGE:
²
Opening 30 ± 4°C
²
Closing
15 ± 4°C
SysCoil 2
SysCoil 2
9.4.1. SYSCOIL 2 SC80
Each fan coil unit is supplied with a 16 mm ID condensate S-shaped pipe. The drain pipe extends approximately
PPRXWRIWKHSLSLQJFRPSDUWPHQWWRHQVXUHHLWKHUʿRRURUZDOOFRQQHFWLRQWRWKHPDLQGUDLQSLSLQJ
For the special case of a horizontal encased HC unit, you must follow the connections as shown below:
9.5. INSTALLATION OF THERMOSTAT OR TEMPERATURE SENSOR (CHANGE OVER)
9.5.1. TRM-FA
9.5.2. TAE20 OR AQUANET OR AQUASIMP