Manufacturer or its representative cannot be held responsible for accidents resulting from
incorrect or non-existent earthing.
Caution
The electrical heating resistances must never operate without ventilation.
Caution
Do not connect several units to a single ventilation speed selector or regulation thermostat
without using auxiliary relays.
Check that the current absorbed by the motors is compatible with the cut-out capacity of the
control device contacts.
Caution
14 SysCoil 2
If the local control includes an remote ambient temperature sensor and/or a set temperature adjustment
module, these shall be connected with shielded cable and shall not pass through the same conduits as the
power supply cables as the voltages induced may create reliability faults in the unit’s operation.
Before making the connections, be sure that the available power supply has the same voltage and phase as
that shown on the fan coil unit nameplate.
Each fan coil unit is supplied with a terminal strip located on the opposite side of piping connections.
Line and low voltage wiring must be done in accordance with electrical code whichever is applicable.
Earthing of unit is imperative.
Note
LIHOHFWULFDOZLULQJRUFRQGXLWFRPHVWKURXJKWKHʿRRUWKH\PXVWEHWLJKWDORQJWKHLUSDVVDJHWKURXJK
WKHʿRRU
10.4. OPTIONAL ELECTRIC HEATER
On request, all fan coil units can be factory mounted with an electric heater.
Do not install the electric heater on existing unit without using the supply air grilles resistant to high
temperature.
)DFWRU\ʾWWHG HOHFWULF KHDWLQJ EDWWHULHV DUH HTXLSSHG ZLWK DQ DXWRPDWLF DQG PDQXDO UHVHW WHPSHUDWXUH
limiting safety device in compliance with IEC 66375.
10.5. CONTROLS
As standard, the units are supplied without regulation equipment.
However, certain control devices (fan speed selector, remote thermostat, etc.) can be supplied according to
request.
If a TRM remote temperature regulation thermostat is supplied, it must only control a single unit. If this
is not the case, you must include a relay box in the circuitry.
(1)
: Available in 2 steps suitable for Aqu@Net control.
Size
SC10
SC20
SC30
SC40
SC50
SC60
SC70
SC80
BE1
W
500
500
500
1250
1250
1250
1000
1500
Mini. air
ʿRZ
m
3
/h
112
112
155
163
230
345
549
665
BE2
W
/
/
1000
(500 + 500)
2500
(1250 + 1250)
2500
(1250 + 1250)
2500
(1250 + 1250)
2000
(1000 + 1000)
3000
(1500 + 1500)
Mini. air
ʿRZ
m
3
/h
/
/
315
230
410
510
549
665