10.5.1.3. TAE20 ROOM THERMOSTAT
10.5.1.3.1. FIELDS OF APPLICATION
²
Regulating ambient temperature in rooms heated or cooled.
²
Opening and closing the valve.
²
Cutting in and out the electric heating.
²
Controlling the three fan speed.
10.5.1.3.2. DESCRIPTION
The unit comprises two parts:
²
A plastic case, housing the electronics, the controls and an internal ambience sensor.
²
A mounting plate.
7KHFDVHLVKRRNHGRQWRWKHʾWWHGPRXQWLQJSODWHWKHQFOLFNIDVWHQHG
The screw terminal connections are located on the mounting plate, with the DIP switches on the back of
the case.
10.5.1.3.3. ADJUSTMENT AND CONTROL ELEMENTS
²
Operating mode switch "ON-OFF" and manual fan
speed selection).
²
Electro-luminescent diodes for displaying the heating
and cooling modes and the fan.
²
Minimum temperature setting limiter (adjustable by
increments of 1 K). Mechanical stop accessible by
removing the button 5.
²
Maximum temperature setting limiter (adjustable by
increments of 1 K). Mechanical stop accessible by
removing the button 5.
²
Ambient temperature setting adjustment button.
²
Set of DIP switches.
DIP
switch ref. 6
Function N°
"ON" position
"OFF" position
1
Fan control
Fan control is temperature
dependent in all modes
In normal mode, the fan control is
independent of the temperature
1
2
Mode changing via an external
switch
Switching between normal mode
and energy saving mode
Switching between normal mode and
stand by
1
3
Switch action direction for external
mode switching
Switch activated when the switch
is closed
(N.O. "Normally open")
1
Switching activated when the switch
is open
(N.C. "Normally close")
4
Stand by
Antifreeze control deactivated
Antifreeze control activated
1
5
Differential
1 K in heating mode
1
0,5 K in cooling mode
4 K in heating mode
2 K in cooling mode
6
Neutral zone in normal mode
2 K
1
)
5 K
7
Temperature setting variance
2 K
1
)
4 K
8
Electric heating
Activated in cooling mode
1
)
Deactivated in cooling mode
1
Factory setting
REFER TO SPECIAL TAE 20 ROOM THERMOSTAT MANUAL