background image

26

   |   Optidrive ODE-3 User Guide   |   

Version 2.00

www.invertekdrives.com

Par.

Description

Minimum Maximum

Default

Units

P-31

Keypad Start  Mode Select

0

7

1

-

This parameter is active only when operating in Keypad Control Mode (P-12 = 1 or 2) or Modbus Mode (P-12 = 3 or 4). When 

settings 0, 1, 4 or 5 are used, the Keypad Start and Stop keys are active, and control terminals 1 and 2 must be linked together. Settings 

2, 3, 6 and 7 allow the drive to be started from the control terminals directly, and the keypad Start and Stop keys are ignored.

0: Minimum Speed, Keypad Start
1: Previous Speed, Keypad Start
2: Minimum Speed, Terminal Enable
3: Previous Speed, Terminal Enable
4: Current Speed, Keypad Start
5: Preset Speed 4, Keypad Start
6: Current Speed, Terminal Start
7: Preset Speed 4, Terminal Start

P-32

Index 1: Duration

0.0

25.0

0.0

s

Index 2: DC Injection Mode

0

2

0

-

Index 1:

 Defines the time for which a DC current is injected into the motor. DC Injection current level may be adjusted in P-59.

Index 2:

 Configures the DC Injection Function as follows:

0: DC Injection on Stop.

 DC is injected into the motor at the current level set in P-59 following a stop command, after the output 

frequency has reduced to P-58 for the time set in Index 1. 

NOTE

  If the drive is in Standby Mode prior to disable, the DC injection is disabled

1: DC Injection on Start.

 DC is injected into the motor at the current level set in P-59 for the time set in Index 1 immediately after 

the drive is enabled, prior to the output frequency ramping up. The output stage remains active during this phase. This can be used to 

ensure the motor is at standstill prior to starting.

2: DC Injection on Start & Stop

. DC injection applied as both settings 0 and 1 above.

P-33

Spin Start

0

2

0

-

0: Disabled
1: Enabled.

 When enabled, on start up the drive will attempt to determine if the motor is already rotating, and will begin to control 

the motor from its current speed. A short delay may be observed when starting motors which are not turning.

2: Enabled on Trip, Brown Out or Coast Stop.

 Spin start is only activated following the events listed, otherwise it is 

disabled.

P-34

Brake Chopper Enable (Not Size 1)

0

4

0

-

0: Disabled
1: Enabled With Software Protection.

 Brake chopper enabled with software protection for a 200W continuous rated 

resistor.

2: Enabled Without Software Protection.

 Enables the internal brake chopper without software protection. An external 

thermal protection device should be fitted.

3: Enabled With Software Protection.

 As setting 1, however the Brake Chopper is only enabled during a change of the 

frequency setpoint, and is disabled during constant speed operation.

4: Enabled Without Software Protection.

 As setting 2, however the Brake Chopper is only enabled during a change of the 

frequency setpoint, and is disabled during constant speed operation.

P-35

Analog Input 1 Scaling / Slave Speed Scaling

0.0

2000.0

100.0

%

Analog Input 1 Scaling. 

The analog input signal level is multiplied by this factor, e.g. if P-16 is set for a 0 – 10V signal, and the 

scaling factor is set to 200.0%, a 5 volt input will result in the drive running at maximum frequency / speed (P-01).

Slave Speed Scaling.

 When operating in Slave Mode (P-12 = 9), the operating speed of the drive will be the Master speed 

multiplied by this factor, limited by the minimum and maximum speeds.

Parameters

6

Содержание Optidrive E3 Series

Страница 1: ...22kW 0 5HP 30HP 1 10 480V 3 Phase Input 1 2 3 4 5 6 7 8 9 10 User Manual Quick Start Up General Information and Ratings Mechanical Installation Power Control Wiring Operation Parameters Analog and Dig...

Страница 2: ...ions 17 4 9 Motor Thermal Overload Protection 18 4 10 EMC Compliant Installation 19 4 1 1 Optional Brake Resistor 19 5 Operation 20 5 1 Managing the Keypad 20 5 2 Operating Displays 20 5 3 Changing Pa...

Страница 3: ...llation or commissioning The manufacturer also accepts no liability for damage or consequences resulting from inappropriate negligent or incorrect installation incorrect adjustment of the operating pa...

Страница 4: ...g to any local legislation or codes Do not carry out any work on the drive control cables whilst power is applied to the drive or to the external control circuits Danger Indicates a potentially hazard...

Страница 5: ...fore connecting the supply 9 5 EMC Filter Disconnect 38 7 Check the supply cable and motor cable for faults or short circuits 8 Route the cables 9 Check that the intended motor is suitable for use not...

Страница 6: ...tentiometer 5k 10k between terminals 5 6 and 7 as shown o Adjust the potentiometer to vary the speed from P 02 0Hz default to P 01 50 60 Hz default Quick Start IP66 Switched Switch the mains power on...

Страница 7: ...Doubler Model Number kW HP Output Current A Frame Size With Filter Without Filter N A ODE 3 1 10023 101 0 5 2 3 1 N A ODE 3 1 10043 101 1 4 3 1 N A ODE 3 210058 104 1 5 5 8 2 200 240V 10 1 Phase Input...

Страница 8: ...4 ODE 3 240041 304 1 5 2 4 1 2 ODE 3 240058 3F4 ODE 3 240058 304 2 2 3 5 8 2 ODE 3 240095 3F4 ODE 3 240095 304 4 5 9 5 2 ODE 3 340140 3F4 ODE 3 340140 304 5 5 7 5 14 3 ODE 3 340180 3F4 ODE 3 340180 30...

Страница 9: ...r the Optidrive given in section 9 1 Environmental Provide suitable clean moisture and contaminant free cooling air sufficient to fulfil the cooling requirements of the Optidrive 3 2 UL Compliant Inst...

Страница 10: ...designed to protect the Optidrive against ingress of airborne dust corrosive gases or liquids conductive contaminants such as condensation carbon dust and metallic particles and sprays or splashing w...

Страница 11: ...0 8 15 189 0 7 44 25 0 0 98 179 0 7 05 161 0 6 34 148 5 5 85 4 0 0 16 8 0 0 31 3 1 6 8 2 257 0 10 12 220 0 8 67 200 0 7 87 28 5 1 12 187 0 7 36 188 0 7 40 176 0 6 93 4 2 0 17 8 5 0 33 4 1 9 0 3 310 0...

Страница 12: ...e heat losses are approximately 3 of operating load conditions Above are guidelines only and the operating ambient temperature of the drive MUST be maintained at all times 3 7 Gland Plate and Lock Off...

Страница 13: ...nection terminals as shown below 0 3 9 Routine Maintenance The drive should be included within the scheduled maintenance program so that the installation maintains a suitable operating environment thi...

Страница 14: ...Earth PE Connection 4 2 1 1 B Incoming Power Connection 4 3 12 C Fuse Circuit Breaker Selection 4 3 2 12 D Optional Input Choke 4 3 3 12 E Optional External EMC Filter 4 10 14 F Internal Disconnect Is...

Страница 15: ...ce must be used The device must be suitable for protecting equipment with a DC component in the leakage current Individual ELCBs should be used for each Optidrive Shield Termination Cable Screen The s...

Страница 16: ...ble is utilised with the shield operating as an earth conductor the shield must have a cross sectional area at least equal to the phase conductors when they are made from the same material Where a 4 c...

Страница 17: ...cal POT In PI Control Local POT controls PI set point Run in Preset Speed Control STOP Run in PI Control 5 0 2 4 5 8 12 In Preset Speed Control P 20 sets the Preset Speed In PI Control POT can control...

Страница 18: ...e analog input e g for speed reference or PID feedback for example is defined by parameters P 15 The function of these parameters and available options is described in section 7 Analog and Digital Inp...

Страница 19: ...nd using an EMC type gland allowing connection to the motor body through the largest possible surface area Where drives are mounted in a steel control panel enclosure the cable screen may be terminate...

Страница 20: ...ive START When in keypad mode used to Start a stopped drive or to reverse the direction of rotation if bi directional keypad mode is enabled 5 2 Operating Displays Drive Stopped Disabled Drive is enab...

Страница 21: ...keys to select the required Read Only parameter Press the Navigate key for 1 second to display the value Press and hold the Navigate key 2 seconds to return to the operating display 5 5 Resetting Para...

Страница 22: ...ons with large sudden step changes in load or for PI control applications Optidrive Energy Optimisation reduces the drive internal heat losses increasing efficiency however it may result in some vibra...

Страница 23: ...ward and reverse directions u using the internal keypad or an external remote Keypad Pressing the keypad START button toggles between forward and reverse 3 Modbus Network Control Control via Modbus RT...

Страница 24: ...will be connected 0 Drive Enabled Running Logic 1 when the motor is enabled 1 Drive Healthy Logic 1 when power is applied to the drive and no fault exists 2 At Target Frequency Speed Logic 1 when the...

Страница 25: ...mit of the band P 28 V F Characteristic Adjustment Voltage 0 P 07 0 V P 29 V F Characteristic Adjustment Voltage 0 0 P 09 0 0 Hz This parameter in conjunction with P 28 sets a frequency point at which...

Страница 26: ...s can be used to ensure the motor is at standstill prior to starting 2 DC Injection on Start Stop DC injection applied as both settings 0 and 1 above P 33 Spin Start 0 2 0 0 Disabled 1 Enabled When en...

Страница 27: ...16 000 0 000 Index 2 Display Scaling Source 0 3 0 Allows the user to program the Optidrive to display an alternative output unit scaled from either output frequency Hz Motor Speed RPM or the signal l...

Страница 28: ...ive will trip and show the fault code if the signal level falls below 3mA 20 to 4mA Signal the Optidrive will run at Preset Speed 1 P 20 if the signal level falls below 3mA Use for motor thermistor me...

Страница 29: ...ance in Ohms Determined by Autotune adjustment is not normally required P 56 Motor Stator d axis Inductance Lsd 0 00 655 35 mH Determined by Autotune adjustment is not normally required P 57 Motor Sta...

Страница 30: ...oing process data TX PDO1 for CAN PO1 PO2 PO3 PO4 P00 23 Accumulated time with heatsink 85 C Hours Total accumulated hours and minutes of operation above heatsink temp of 85 C P00 24 Accumulated time...

Страница 31: ...w of the functions of each terminal macro function and a simplified connection diagram for each 7 2 Macro Functions Guide Key The table below should be used as a key for pages 32 to 34 STOP RUN Latche...

Страница 32: ...nalog Input AI1 3 FAST STOP P 24 8 STOP RUN FWD REV DI3 DI4 PR 2 0 0 P 20 1 0 P 21 0 1 P 22 1 1 P 23 9 STOP START FWD STOP START REV DI3 DI4 PR 2 FAST STOP P 24 0 0 P 20 1 0 P 21 0 1 P 22 1 1 P 23 10...

Страница 33: ...Mode FWD REV 2 18 STOP RUN AI1 REF KPD REF Fire Mode AI1 1 9 10 11 12 13 0 7 5 Macro Functions Fieldbus Control Mode P 12 3 4 7 8 or 9 P 15 DI1 DI2 DI3 AI2 DI4 AI1 Diagram 0 1 0 1 0 1 0 1 0 STOP ENABL...

Страница 34: ...conditions until the drive is no longer capable of sustaining operation The Fire Mode input may be a normally open Close to Activate Fire Mode or Normally Closed Open to Activate Fire Mode according t...

Страница 35: ...ram 8 NO NC Close Open Start Stop NO NC NO Close Open Close FWD Stop REV NC Open Fast Stop P 24 NO NO Speed Diagram 9 Diagram 10 Diagram 11 Diagram 12 NO NC NO Speed Open Speed E Trip NO NC NC Open Tr...

Страница 36: ...t 0 Low Stop High Run Enable Bit 1 Low Decel Ramp 1 P 04 High Decel Ramp 2 P 24 Bit 2 Low No Function High Fault Reset Bit 3 Low No Function High Coast Stop Request 2 R W Modbus Speed reference setpoi...

Страница 37: ...3 25 200 240 10 V 3 Phase Input 3 Phase Output 1 0 37 0 5 3 4 6 6 8 8 2 3 1 0 75 1 5 6 10 10 8 8 4 3 1 1 5 2 9 5 16 15 8 8 7 2 1 5 2 8 9 16 15 8 8 7 100 2 2 2 3 12 1 16 17 5 8 8 10 5 50 3 4 5 20 9 32...

Страница 38: ...ected according to the data shown in section 9 2 Rating Tables and the National Electrical Code or other applicable local codes Motor Cable 75 C Copper must be used Power cable connections and tighten...

Страница 39: ...t has opened for some reason If motor thermistor is connected check if the motor is too hot 12 Optibus comms loss Check communication link between drive and external devices Make sure each drive in th...

Страница 40: ...82 E3MAN IN_V2 00Z 82 E3MAN IN_V2 00 Invertek Drives Ltd Offa s Dyke Business Park Welshpool Powys SY21 8JF United Kingdom Tel 44 0 1938 556868 Fax 44 0 1938 556869 www invertekdrives com...

Отзывы: