background image

Version 2.00

   |   Optidrive ODE-3 User Guide   |   

3

www.invertekdrives.com

Declaration of Conformity

Invertek Drives Ltd hereby states that the Optidrive ODE-3 product range conforms to the relevant safety provisions of the following 
council directives:
2014/30/EU (EMC) and 2014/35/EU (LVD)
Designed and manufacture is in accordance with the following harmonised European standards:

EN 61800-5-1: 2007

Adjustable speed electrical power drive systems. Safety 
requirements. Electrical, thermal and energy.

EN 61800-3: 2004 /A1 2012

Adjustable speed electrical power drive systems. EMC 
requirements and specific test methods

EN 55011: 2007

Limits and Methods of measurement of radio disturbance 
characteristics of industrial, scientific and medical (ISM) radio-
frequency equipment (EMC)

EN60529: 1992

Specifications for degrees of protection provided by enclosures

Electromagnetic Compatibility

All Optidrives are designed with high standards of EMC in mind. All versions suitable for operation on Single Phase 230 volt and 
Three Phase 400 volt supplies and intended for use within the European Union are fitted with an internal EMC filter. This EMC filter 
is designed to reduce the conducted emissions back into the mains supply via the power cables for compliance with the above 
harmonised European standards.
It is the responsibility of the installer to ensure that the equipment or system into which the product is incorporated complies with the 
EMC legislation of the country of use, and the relevant category. Within the European Union, equipment into which this product is 
incorporated must comply with the EMC Directive 2004/108/EC. This User Guide provides guidance to ensure that the applicable 
standards may be achieved.

Copyright Invertek Drives Ltd © 2016

All rights reserved. No part of this User Guide may be reproduced or transmitted in any form or by any means, electrical or mechanical 
including photocopying, recording or by any information storage or retrieval system without permission in writing from the publisher.

2 Year Warranty

All Invertek Optidrive units carry a 2 year warranty against manufacturing defects from the date of manufacture. The manufacturer 
accepts no liability for any damage caused during or resulting from transport, receipt of delivery, installation or commissioning. The 
manufacturer also accepts no liability for damage or consequences resulting from inappropriate, negligent or incorrect installation, 
incorrect adjustment of the operating parameters of the drive, incorrect matching of the drive to the motor, incorrect installation, 
unacceptable dust, moisture, corrosive substances, excessive vibration or ambient temperatures outside of the design specification.
The local distributor may offer different terms and conditions at their discretion, and in all cases concerning warranty, the local 
distributor should be contacted first.

This user guide is the “original instructions” document. All non-English versions are translations of the 

“original instructions”.

The contents of this User Guide are believed to be correct at the time of printing. In the interest of a commitment to a policy of 
continuous improvement, the manufacturer reserves the right to change the specification of the product or its performance or the 
contents of the User Guide without notice.

This User Guide is for use with version 3.05 Firmware
User Guide Revision 2.00

Invertek Drives Ltd adopts a policy of continuous improvement and whilst every effort has been made to provide accurate and up to 
date information, the information contained in this User Guide should be used for guidance purposes only and does not form the part 
of any contract.

This manual is intended as a guide for proper installation. Invertek Drives Ltd cannot assume responsibility for the compliance 

or the non-compliance to any code, national, local or otherwise, for the proper installation of this drive or associated 

equipment. A hazard of personal injury and/or equipment damage exists if codes are ignored during installation.
This Optidrive contains high voltage capacitors that take time to discharge after removal of the main supply. Before 

working on the drive, ensure isolation of the main supply from line inputs. Wait ten (10) minutes for the capacitors to 

discharge to safe voltage levels. Failure to observe this precaution could result in severe bodily injury or loss of life.
Only qualified electrical personnel familiar with the construction and operation of this equipment and the hazards involved 

should install, adjust, operate, or service this equipment. Read and understand this manual and other applicable manuals 

in their entirety before proceeding. Failure to observe this precaution could result in severe bodily injury or loss of life.

Содержание Optidrive E3 Series

Страница 1: ...22kW 0 5HP 30HP 1 10 480V 3 Phase Input 1 2 3 4 5 6 7 8 9 10 User Manual Quick Start Up General Information and Ratings Mechanical Installation Power Control Wiring Operation Parameters Analog and Dig...

Страница 2: ...ions 17 4 9 Motor Thermal Overload Protection 18 4 10 EMC Compliant Installation 19 4 1 1 Optional Brake Resistor 19 5 Operation 20 5 1 Managing the Keypad 20 5 2 Operating Displays 20 5 3 Changing Pa...

Страница 3: ...llation or commissioning The manufacturer also accepts no liability for damage or consequences resulting from inappropriate negligent or incorrect installation incorrect adjustment of the operating pa...

Страница 4: ...g to any local legislation or codes Do not carry out any work on the drive control cables whilst power is applied to the drive or to the external control circuits Danger Indicates a potentially hazard...

Страница 5: ...fore connecting the supply 9 5 EMC Filter Disconnect 38 7 Check the supply cable and motor cable for faults or short circuits 8 Route the cables 9 Check that the intended motor is suitable for use not...

Страница 6: ...tentiometer 5k 10k between terminals 5 6 and 7 as shown o Adjust the potentiometer to vary the speed from P 02 0Hz default to P 01 50 60 Hz default Quick Start IP66 Switched Switch the mains power on...

Страница 7: ...Doubler Model Number kW HP Output Current A Frame Size With Filter Without Filter N A ODE 3 1 10023 101 0 5 2 3 1 N A ODE 3 1 10043 101 1 4 3 1 N A ODE 3 210058 104 1 5 5 8 2 200 240V 10 1 Phase Input...

Страница 8: ...4 ODE 3 240041 304 1 5 2 4 1 2 ODE 3 240058 3F4 ODE 3 240058 304 2 2 3 5 8 2 ODE 3 240095 3F4 ODE 3 240095 304 4 5 9 5 2 ODE 3 340140 3F4 ODE 3 340140 304 5 5 7 5 14 3 ODE 3 340180 3F4 ODE 3 340180 30...

Страница 9: ...r the Optidrive given in section 9 1 Environmental Provide suitable clean moisture and contaminant free cooling air sufficient to fulfil the cooling requirements of the Optidrive 3 2 UL Compliant Inst...

Страница 10: ...designed to protect the Optidrive against ingress of airborne dust corrosive gases or liquids conductive contaminants such as condensation carbon dust and metallic particles and sprays or splashing w...

Страница 11: ...0 8 15 189 0 7 44 25 0 0 98 179 0 7 05 161 0 6 34 148 5 5 85 4 0 0 16 8 0 0 31 3 1 6 8 2 257 0 10 12 220 0 8 67 200 0 7 87 28 5 1 12 187 0 7 36 188 0 7 40 176 0 6 93 4 2 0 17 8 5 0 33 4 1 9 0 3 310 0...

Страница 12: ...e heat losses are approximately 3 of operating load conditions Above are guidelines only and the operating ambient temperature of the drive MUST be maintained at all times 3 7 Gland Plate and Lock Off...

Страница 13: ...nection terminals as shown below 0 3 9 Routine Maintenance The drive should be included within the scheduled maintenance program so that the installation maintains a suitable operating environment thi...

Страница 14: ...Earth PE Connection 4 2 1 1 B Incoming Power Connection 4 3 12 C Fuse Circuit Breaker Selection 4 3 2 12 D Optional Input Choke 4 3 3 12 E Optional External EMC Filter 4 10 14 F Internal Disconnect Is...

Страница 15: ...ce must be used The device must be suitable for protecting equipment with a DC component in the leakage current Individual ELCBs should be used for each Optidrive Shield Termination Cable Screen The s...

Страница 16: ...ble is utilised with the shield operating as an earth conductor the shield must have a cross sectional area at least equal to the phase conductors when they are made from the same material Where a 4 c...

Страница 17: ...cal POT In PI Control Local POT controls PI set point Run in Preset Speed Control STOP Run in PI Control 5 0 2 4 5 8 12 In Preset Speed Control P 20 sets the Preset Speed In PI Control POT can control...

Страница 18: ...e analog input e g for speed reference or PID feedback for example is defined by parameters P 15 The function of these parameters and available options is described in section 7 Analog and Digital Inp...

Страница 19: ...nd using an EMC type gland allowing connection to the motor body through the largest possible surface area Where drives are mounted in a steel control panel enclosure the cable screen may be terminate...

Страница 20: ...ive START When in keypad mode used to Start a stopped drive or to reverse the direction of rotation if bi directional keypad mode is enabled 5 2 Operating Displays Drive Stopped Disabled Drive is enab...

Страница 21: ...keys to select the required Read Only parameter Press the Navigate key for 1 second to display the value Press and hold the Navigate key 2 seconds to return to the operating display 5 5 Resetting Para...

Страница 22: ...ons with large sudden step changes in load or for PI control applications Optidrive Energy Optimisation reduces the drive internal heat losses increasing efficiency however it may result in some vibra...

Страница 23: ...ward and reverse directions u using the internal keypad or an external remote Keypad Pressing the keypad START button toggles between forward and reverse 3 Modbus Network Control Control via Modbus RT...

Страница 24: ...will be connected 0 Drive Enabled Running Logic 1 when the motor is enabled 1 Drive Healthy Logic 1 when power is applied to the drive and no fault exists 2 At Target Frequency Speed Logic 1 when the...

Страница 25: ...mit of the band P 28 V F Characteristic Adjustment Voltage 0 P 07 0 V P 29 V F Characteristic Adjustment Voltage 0 0 P 09 0 0 Hz This parameter in conjunction with P 28 sets a frequency point at which...

Страница 26: ...s can be used to ensure the motor is at standstill prior to starting 2 DC Injection on Start Stop DC injection applied as both settings 0 and 1 above P 33 Spin Start 0 2 0 0 Disabled 1 Enabled When en...

Страница 27: ...16 000 0 000 Index 2 Display Scaling Source 0 3 0 Allows the user to program the Optidrive to display an alternative output unit scaled from either output frequency Hz Motor Speed RPM or the signal l...

Страница 28: ...ive will trip and show the fault code if the signal level falls below 3mA 20 to 4mA Signal the Optidrive will run at Preset Speed 1 P 20 if the signal level falls below 3mA Use for motor thermistor me...

Страница 29: ...ance in Ohms Determined by Autotune adjustment is not normally required P 56 Motor Stator d axis Inductance Lsd 0 00 655 35 mH Determined by Autotune adjustment is not normally required P 57 Motor Sta...

Страница 30: ...oing process data TX PDO1 for CAN PO1 PO2 PO3 PO4 P00 23 Accumulated time with heatsink 85 C Hours Total accumulated hours and minutes of operation above heatsink temp of 85 C P00 24 Accumulated time...

Страница 31: ...w of the functions of each terminal macro function and a simplified connection diagram for each 7 2 Macro Functions Guide Key The table below should be used as a key for pages 32 to 34 STOP RUN Latche...

Страница 32: ...nalog Input AI1 3 FAST STOP P 24 8 STOP RUN FWD REV DI3 DI4 PR 2 0 0 P 20 1 0 P 21 0 1 P 22 1 1 P 23 9 STOP START FWD STOP START REV DI3 DI4 PR 2 FAST STOP P 24 0 0 P 20 1 0 P 21 0 1 P 22 1 1 P 23 10...

Страница 33: ...Mode FWD REV 2 18 STOP RUN AI1 REF KPD REF Fire Mode AI1 1 9 10 11 12 13 0 7 5 Macro Functions Fieldbus Control Mode P 12 3 4 7 8 or 9 P 15 DI1 DI2 DI3 AI2 DI4 AI1 Diagram 0 1 0 1 0 1 0 1 0 STOP ENABL...

Страница 34: ...conditions until the drive is no longer capable of sustaining operation The Fire Mode input may be a normally open Close to Activate Fire Mode or Normally Closed Open to Activate Fire Mode according t...

Страница 35: ...ram 8 NO NC Close Open Start Stop NO NC NO Close Open Close FWD Stop REV NC Open Fast Stop P 24 NO NO Speed Diagram 9 Diagram 10 Diagram 11 Diagram 12 NO NC NO Speed Open Speed E Trip NO NC NC Open Tr...

Страница 36: ...t 0 Low Stop High Run Enable Bit 1 Low Decel Ramp 1 P 04 High Decel Ramp 2 P 24 Bit 2 Low No Function High Fault Reset Bit 3 Low No Function High Coast Stop Request 2 R W Modbus Speed reference setpoi...

Страница 37: ...3 25 200 240 10 V 3 Phase Input 3 Phase Output 1 0 37 0 5 3 4 6 6 8 8 2 3 1 0 75 1 5 6 10 10 8 8 4 3 1 1 5 2 9 5 16 15 8 8 7 2 1 5 2 8 9 16 15 8 8 7 100 2 2 2 3 12 1 16 17 5 8 8 10 5 50 3 4 5 20 9 32...

Страница 38: ...ected according to the data shown in section 9 2 Rating Tables and the National Electrical Code or other applicable local codes Motor Cable 75 C Copper must be used Power cable connections and tighten...

Страница 39: ...t has opened for some reason If motor thermistor is connected check if the motor is too hot 12 Optibus comms loss Check communication link between drive and external devices Make sure each drive in th...

Страница 40: ...82 E3MAN IN_V2 00Z 82 E3MAN IN_V2 00 Invertek Drives Ltd Offa s Dyke Business Park Welshpool Powys SY21 8JF United Kingdom Tel 44 0 1938 556868 Fax 44 0 1938 556869 www invertekdrives com...

Отзывы: