Version 1.00
| Optidrive CoolVert User Guide |
23
www.invertekdrives.com
4
Set-up and Operation
4.1.7. System Tuning
Par.
Mod Add Description
Def
Min
Max
Unit
R/W
5-03
503
Vector Speed Controller Proportional Gain
50
0.1
400
%
R/W
5-04
504
Vector Speed Controller Integral Time Constant
0.050
0.001
2.00
s
R/W
7-01
701
Minimum Switching Frequency – Thermal Management
-
-
-
kHz
R/W
7-02
702
Auto-reset Delay
20
1
60
S
R/W
7-03
703
Motor Stator Resistance (Rs) phase to phase
W
R/W
7-04
704
Motor Stator Inductance (Lsd) per phase
mH
R/W
7-05
705
Motor Stator Inductance (Lsq) per phase
mH
R/W
7-06
706
V/F Mode Magnetising Period
-
0
5000
Ms
R/W
7-07
707
Low Frequency Torque Boost Level
0.0
0.0
100
%
R/W
7-08
708
Low Frequency Torque Boost, Frequency Limit
0.0
0.0
50
%
R/W
The values for P7-03 through to P7-05 are gathered by the drive during the autotune process.
4.1.8. Thermal Protection
Par.
Mod Add Description
Def
Min
Max
Unit
R/W
5-07
507
Maximum Current Limit
110
20
150
%
R/W
5-08
508
Motor Power Limit
130
0
130
%
R/W
5-09
509
Motor Thermal Overload Management (Ixt)
0
0
1
-
R/W
5-10
510
Drive Thermal Overload Management
(Drive Temperature Based)
0
0
1
-
R/W
5-11
511
Motor Thermal Overload Retention Enable
1
0
1
-
R/W
7-01
701
Minimum Switching Frequency – Thermal Management
-
-
-
kHz
R/W
7-02
702
Auto-reset Delay
20
1
60
S
R/W
4.2. Modbus Connections
4.2.1 Minimum Control Wiring Required For Each Control Mode
See parameter 1-11 in section
P1-11 = 0 - Modbus control
0V C
ommon
Modbus TX/RX +
Modbus TX/RX -
+2
4V Output (1
00mA)
Digital Input 1
Analogue Input 1
0V C
ommon
ST
O
+
ST
O
-
User R
elay A
User R
elay B
1
2
3
4
5
6
7
8
9
10
11
STO signal must be provided in order to permit running the motor. Start/Stop commands and speed reference are provided by serial
communication. In Modbus mode, the digital input and analogue input can be used as remote I/O by the controller, the relay output
can also be configured to be controlled by Modbus and used by the controller if required.