6.6.11. User Register 1 / User Register 2
For P2 and Eco drives, which have internal function block programming capability, data may be read from the User Registers. This
allows control functions to be achieved within the drive by linking to the Group 9 parameters. The values may also be used within the
function block program.
6.6.12. P0-80 Value
For Optidrive P2 and Eco models, Parameter P0-80 may be used to display internal data from the drive. Refer to the drive
documentation for further information.
6.7. OPT-2-ETHEG-IN Web Server
The OPT-2-ETHEG-IN web server interface can be accessed at via the IP address or host name.
Default IP address: 192.168.1.254
Hostname: OPCxxxxxxxxxx, where xxxxxxxxxx = ‘PR ID’ value shown on the top product label as described in section
2.2. Labelling.
Both of the above values can be modified via the Web Server or Ethernet/IP Class 0xF4.
The Webserver contains 4 pages as described below.
6.7.1. Module Configuration
Information about the Ethernet IP Interface is displayed. The information is Read Only.
6.7.2. Module Identity
Information about the Module Identity (Class 0x01) is displayed. The information is Read Only.