16
| Optidrive ODP-2ETHEG-IN |
Version 1.10
www.invertekdrives.com
Bit
Function
E3
P2
Eco
0
0: Drive Disabled (Stopped)
1: Drive Enabled (Running)
✔
✔
✔
1
0: Drive Healthy
1: Drive Tripped
✔
✔
✔
2
0: Auto
1: Hand
✔
3
0: Drive Ready (STO Input Closed)
1: Drive Inhibit (STO Input Option
✔
✔
4
0: Maintenance Time Not Reached
1: Maintenance Time Reached
✔
✔
5
0: Not In Standby (Sleep)
1: Standby (Sleep) mode active
✔
✔
6
0: Not Ready
1: Drive Ready (Mains Power applied, No Inhibit, No Trip, Enable Input Present)
✔
✔
7
0: No Warning
1: Motor Load Current Outside bandwidth
✔
8 - 15
Fault code number. Refer to the table in section 0.
✔
✔
✔
6.6.2. Drive Fault Codes
The following table provides a list of the possible fault code numbers returned in the Drive Stratus Word High Byte, and the relevant
fault information for each code. Refer to the relevant drive User Guide for further information on the cause and possible solutions for
each fault.
No.
Fault Description
00
No fault.
01
Brake channel over current.
02
Brake resistor overload.
03
Instantaneous over current on drive output.
04
Excess load on the motor.
05
Drive has tripped on overload after delivering >100% of value in P1-08 for a period of time.
06
Hardware over current.
07
Over voltage on DC bus.
08
Under voltage on DC bus.
09
Heatsink over temperature.
10
Under temperature.
11
Factory default parameters have been loaded.
12
External trip.
13
Communications fault.
14
Excessive DC Ripple.
15
Input phase loss trip.
16
Instantaneous over current on drive output.
17
Faulty thermistor on heatsink.
18
Internal memory fault.
19
4-20mA signal lost.
20
Internal memory fault.
21
User parameter defaults.
22
Motor PTC over temperature.
23
Cooling fan fault.
Operation
6