8
| Optidrive Eco User Guide |
Version 3.07
www.invertekdrives.com
2.1.4. Low Harmonic Variants
The majority of the Optidrive Eco product range is based on a low harmonic solution using film capacitor technology to achieve
compliance with EN 61000-3-12 without the need for any additional equipment. This standard specifies limits for harmonic currents
for equipment connected to public low-voltage systems with input current > 16A and <= 75A per phase. It is important to understand
which models from the product range are of the low harmonic technology which is detailed below.
The Optidrive Eco three phase 200V (200-240V) input and three phase 400V (380-480V) input drives frame sizes 2 up to and
including frame size 5 are a lower harmonic drive using film capacitor technology. Please refer to the product rating tables in section
In short, this means that the low harmonic drives do not require an input choke and should not have one installed – drives outside of
the above frame sizes and supply voltage / number of phases, are of standard electrolytic capacitor design and could benefit from
the use of input chokes if further harmonic reduction is required.
2.2. Identifying the Drive by Model Number
Each drive can be identified by its model number, shown below. The model number is on the shipping label and the drive nameplate.
The model number includes the drive and factory fitted options.
ODV -
3
-
4
4
0460 -
3
F
1
N - M
N
Product Range
ODV: Eco Series
PCB Coating
N : Standard Localised Coating
Display
T : OLED Text Display
M: TFT Display
Generation
Frame Size
Voltage Code
2 : 200 – 240
4 : 380 – 480
6 : 500 – 600
Enclosure
2 : IP20
N : IP55
A : IP66 Non-Switched
E : IP66 With Disconnect
Output Current
Shown with 1 decimal place
Brake Transistor
1 : No Brake Transistor
Supply Phase
1 : 1 Phase Input
3 : 3 Phase Input
EMC Filter
0 : No Internal Filter
F : Internal EMC Filter
2
General Information and Ratings