Version 3.07
| Optidrive Eco User Guide |
3
www.invertekdrives.com
Declaration of Conformity
Invertek Drives Ltd hereby states that the Optidrive Eco product range conforms to the relevant safety provisions of the following council directives:
2014/30/EU (EMC) and 2014/35/EU (LVD)
Design and manufacture is in accordance with the following harmonised European standards:
EN 61800-5-1: 2003
Adjustable speed electrical power drive systems. Safety requirements. Electrical, thermal and energy.
EN 61800-3 2nd Ed: 2004 Adjustable speed electrical power drive systems. EMC requirements and specific test methods.
EN61000-3-12
Limits for harmonic currents produced by equipment connected to public low-voltage systems with input current > 16
A and <= 75 A per phase.
Three phase 200V and three phase 400V Optidrive Eco products comply with IEC 61000-3-12 with respect to the
THC without the need for Line Reactors, provided that the short-circuit power Ssc is greater than or equal to SSC
(min) at the interface point between the user's supply and the public system. It is the responsibility of the installer or
user of the equipment to ensure, by consultation with the distribution network operator if necessary, that the equipment
is connected only to a supply with a short-circuit power
S
SC
greater than or equal to
S
SC (min)
calculated as:
S
SC (min)
=320 ×
V
rated
×
I
rated
Where
V
rated
is the drive rated voltage (phase to phase) and
I
rated
is the drive rated current (per phase)
EN 55011: 2007
Limits and Methods of measurement of radio disturbance characteristics of industrial, scientific and medical (ISM)
radio-frequency equipment (EMC).
EN60529: 1992
Specifications for degrees of protection provided by enclosures.
Safe Torque OFF (“STO”) Function
Optidrive Eco incorporates a hardware STO (Safe Torque Off) Function, designed in accordance with the standards listed below.
Standard
Classification
Independent Approval
EN 61800-5-2:2016
Type 2
*TUV
EN ISO 13849-1:2015
PL “d”
EN 61508 (Part 1 to 7):2010
SIL 2
EN60204-1:2006 + A1:2009 + AC: 2010
Uncontrolled Stop “Category 0”
EN 62061:2005/A2:2015
SIL CL 2
Electromagnetic Compatibility
All Optidrives are designed with high standards of EMC in mind. All versions intended for use within the European Union are fitted with an internal
EMC filter. This EMC filter is designed to reduce the conducted emissions back into the supply via the power cables for compliance with harmonised
European standards.
It is the responsibility of the installer to ensure that the equipment or system into which the product is incorporated complies with the EMC legislation
of the country of use. Within the European Union, equipment into which this product is incorporated must comply with the EMC Directive 2014/30/
EU. When using an Optidrive with an internal or optional external filter, compliance with the following EMC Categories, as defined by EN61800-
3:2004 can be achieved:
Copyright Invertek Drives Ltd © 2020
All rights reserved. No part of this User Guide may be reproduced or transmitted in any form or by any means, electrical or mechanical including
photocopying, recording or by any information storage or retrieval system without permission in writing from the publisher.
2 Year Warranty:
All Invertek Optidrive Eco units carry a 2 year warranty against manufacturing defects from the date of manufacture.
The manufacturer accepts no liability for any damage caused during or resulting from transport, receipt of delivery, installation or commissioning.
The manufacturer also accepts no liability for damage or consequences resulting from inappropriate, negligent or incorrect installation, incorrect
adjustment of the operating parameters of the drive, incorrect matching of the drive to the motor, incorrect installation, unacceptable dust, moisture,
corrosive substances, excessive vibration or ambient temperatures outside of the design specification.
The local distributor may offer different terms and conditions at their discretion, and in all cases concerning warranty, the local distributor should be
contacted first.
This user guide is the “original instructions” document. All non-English versions are translations of the “original instructions”.
The contents of this User Guide are believed to be correct at the time of printing. In the interest of a commitment to a policy of continuous improvement,
the manufacturer reserves the right to change the specification of the product or its performance or the contents of the User Guide without notice.
This User Guide is for use with version 2.50 Firmware. The firmware version can be viewed in
parameter P0-28. User Guide Revision 3.07
Invertek Drives Ltd adopts a policy of continuous improvement and whilst every effort has been made to provide accurate and up to date information, the
information contained in this User Guide should be used for guidance purposes only and does not form the part of any contract.
When installing the drive on any power supply where the phase-ground voltage may exceed the phase-phase voltage (typically IT
supply networks or Marine vessels) it is essential that the internal EMC filter ground and surge protection varistor ground (where fitted) are
disconnected. If in doubt, refer to your Sales Partner for further information.
This manual is intended as a guide for proper installation. Invertek Drives Ltd cannot assume responsibility for the compliance or the
non-compliance to any code, national, local or otherwise, for the proper installation of this drive or associated equipment. A hazard of
personal injury and/or equipment damage exists if codes are ignored during installation.
This Optidrive contains high voltage capacitors that take time to discharge after removal of the main supply. Before working on the
drive, ensure isolation of the main supply from line inputs. Wait ten (10) minutes for the capacitors to discharge to safe voltage levels.
Failure to observe this precaution could result in severe bodily injury or loss of life.
Only qualified electrical personnel familiar with the construction and operation of this equipment and the hazards involved should
install, adjust, operate, or service this equipment. Read and understand this manual and other applicable manuals in their entirety before
proceeding. Failure to observe this precaution could result in severe bodily injury or loss of life.