62
| Optidrive Eco User Guide |
Version 3.07
www.invertekdrives.com
Analog Value Object
Analog Value Objects Table
Instance ID
Object Name
Access
Description
Units
AV0
Motor Frequency
R
Motor output frequency
Hertz
AV1
Motor Speed
R
Motor output speed (0 if P1-10=0)
Rpm
AV2
Motor Current
R
Motor output current
Amps
AV3
Motor Power
R
Motor output power
Kilowatts
AV4
Motor torque
R
Reserved
%
AV5
DC Bus Voltage
R
DC bus voltage
Volts
AV6
Drive temperature
R
Drive temperature value
°
C
AV7
Drive Status
R
Drive status word
NONE
AV8
Trip Code
R
Drive trip code
NONE
AV9
Analog input 1
R
Value of analog input 1
Percent
AV10
Analog input 2
R
Value of analog input 2
Percent
AV11
Analog output 1
R
Value of analog output 1
Percent
AV12
Analog output 2
R
Value of analog output 2
Percent
AV13
PID Reference
R
PID controller reference value
Percent
AV14
PID feedback
R
PID controller feedback value
Percent
AV15
Speed Reference
C
Speed reference value object
Hertz
AV16
User Ramp Time
W
User ramp value
Seconds
AV17
User PID Reference
W
PID controller user reference
Percent
AV18
User PID Feedback
W
PID controller user feedback
Percent
AV19
Kilowatt Hours
R
Kilowatt hours (can be reset by user)
Kilowatt-hours
AV20
Megawatt Hours
R
Megawatt hours (can be reset by user)
Megawatt-hours
AV21
KWh meter
R
Kilowatt hours meter (cannot be reset)
Kilowatt-hours
AV22
MWh meter
R
Megawatt hours meter (cannot be reset)
Megawatt-hours
AV23
Total Run Hours
R
Total run hours since date of manufacture
Hours
AV24
Current Run Hours
R
Run hours since last time enable
Hours
* This function only works if the relay output can be controlled by user value (Refer to the Optidrive Eco Parameter List for further details)
10.3.6. Access type
R - Read only
W - Read or Write
C - Commandable
10.3.7. Supported Service
WHO-IS (Reply with I-AM, and I-AM will also be broadcasted on power up and reset)
WHO-HAS (Reply with I-HAVE)
Read Property
Write Property
Device Communication Control
Reinitialize Device
10
Serial Communications