![inVENTer sMove Скачать руководство пользователя страница 11](http://html.mh-extra.com/html/inventer/smove/smove_user-manual_2083852011.webp)
11
SPECIFICATIONS
iV-Smart
+
ventilation system
•
Installation instructions
3
Specifications
3.1
General specifications
Feature
Value
Operating range [°C]
-20 – 50
Extract air/Outdoor air
Free from aggressive gases, dust and oils
Air flow in reverse operation (push-pull) per unit
[m³/h]
8.5 – 29
Extract air flow per unit [m³/h] (EN 13141-8)
17 – 58
Sound pressure level [dB (A)]
16 – 36
Standard sound level differential [dB]
Standard: 38 – 49
Corner: 39 – 47
Ohio: 34
Heat recovery [η'
w
]
0.87
Output voltage [V DC]
6 – 16
Power consumption [W]
1 – 3
Flow based electrical fan capacity [W/(m³/h)]
0.15
Protection class (EN 61140)
III
Type of protection (EN 60529)
IP20
Filter class (standard filter) (EN 779:2012)
G4
Air flow sensitivity at ± 20 Pa (EN 13141-8)
S3
Frost protection
Automatically due to push-pull operation
(up to -20 °C)
Weight [g]
Max. 5390
(with Smart protective hood)
Max. 5330
(with Nova protective hood)
Max. 6150
(with Corner exterior closure)
Max. 5670
(with Ohio protective hood)
Conformity