intensity IMCH-036KC-3 Скачать руководство пользователя страница 7

CAUTION

CAUTION

CAUTION

6

6.9 Size and position of connections

Model

  36/60 Btus

6.8 Emptying the installation

A (mm)

300

B (mm)

195

C (mm)

155

D (mm)

E (mm)
F (mm)

Water inlet/outlet (Ø)

Auto-water replenishing (Ø)

Security discharge

(Ø)

F

water outlet

auto-water

replenishing orifice

security discharge

 water inlet

105

 68

105

 R5/4

G1/2
G1/2

An all-pole disconnection device which has at least 3mm
separation distance in all pole and a residual current device
(RCD) with the rating of above 10mA shall be incorporated in the
fixed wiring according to the national rule the appliance shall be
installed in accordance with national wiring regulations.

6.7 Filling the installation

-Before filling,check that the installation drain cock is closed.
-Open all installation and terminal air vents.
-Open the gate valves.
-Begin filling,slowly opening the water filling cock outside the unit.
-When water begins to leak out of the terminal air vent valves,
 close them and continue filling until the pressure gauge indicates
 a pressure of 1.5 bars.

-Before emptying,place the mains switch in the “off ” position.
-Make sure the installation fill/top-up water cock is closed.
-Open the drain cock outside the unit and all the installation and
  terminal air vent valves.

The installation must be filled to a pressure of between 1 and
2 bars.
It is recommended that this operation be repeated after the unit
has been operating for a number of hours.The pressure of the
installation should be checked regularly and if it drops below
1 bar,the water content should be topped-up.
Check the  hydraulic tightness of joints.

If the fluid in the circuit contains anti-freeze,it should not be
allowed to drain freely as it is pollutant.It should be collected
for possible reuse.When draining after heat pump operation,
take care as the water may be hot (up to 50°).

6.4 Maximum chilled water flow

The maximum chilled water flow is limited by the permitted
pressure drop in the evaporator. It is provided in the table 6-1

If the system flow is more than the maximum unit flow rate,
bypass the evaporator as shown in the diagram to obtain a lower
evaporator flow rate.

For maximum chilled water flow rate

6.5 Minimum and Maximum water flow rates

Evaporator

Recirculation

Table 6-1

Water flow rate(m

3

/h)

Maximum

Minimum

Item

Model

IMCH-036KC-3

IMCH-060KC-3

2.63

3.22

1.89

1.54

6.6 Water quality control

When industrial water is used as chilled water, little furring may
occur; however, well water or river water, used as chilled water,
may cause much sediment, such as furring, sand, and so on.
Therefore, well water or river water must be filtered and softened
in softening water equipment before flowing into chilled water
system. If sand and clay settle in the evaporator, circulation of
chilled water may be blocked, and thus leading to freezing
accidents; if hardness of chilled water is too high, furring may
occur easily, and the devices may be corroded. Therefore, the
quality of chilled water should be analyzed before being used,
such as PH value, conductivity, concentration of chloride ion,
concentration of sulfide ion, and so on.

<50ppm

<50ppm

<30ppm

<200

ȝ

V/cm(25ºC)

<0.3ppm

<50ppm

<50ppm

6.6.2 Applicable standard of water quality for the unit

PH value

Total hardness

Conductivity

Sulfide ion

Chloride ion

Ammonia ion

Sulfate ion

Silicon

Iron content

Sodium ion

Calcium ion

No

No

No requirement

Table 6-2

6

 

8

6.6.1 Water quality control

Table 6-3

Содержание IMCH-036KC-3

Страница 1: ...MINI CHILLER MAN IO IMCH 0615 intensity mx INSTALLATION OWNER S MANUAL IMCH 036KC 3 IMCH 060KC 3 3 and 5 Tons...

Страница 2: ...result in cutting injuries Never inspect or service the unit by yourself Ask a qualified service person to perform this work Do not dispose this product as unsorted municipal waste Collection of such...

Страница 3: ...ide Failure to observe could cause the chemicals to become deposited in the unit which could endanger the health of those who are hypersensitive to chemicals Do not place appliances which produce open...

Страница 4: ...LowPressureSwitch 12 DischargeGasthermistor 13 thermistor For Outdoor Temperature 14 Thermistor For EvaporationInHeating Thermistor For Condenser InCooling 15 Thermistor For PlateHeat Exchange1 16 The...

Страница 5: ...Never hold the inlet of the outdoor unit to prevent it from deforming 5 4 Water Outlet Reserve water outlet Reserve water outlet Water Outlet Outlet for power and connecting pipes Need to knock open...

Страница 6: ...containinganti freeze or covered by specific legislation must be fitted with hydraulic disconnectors The manufactureris not liable for obstruction breakage or noise resulting from the failure to insta...

Страница 7: ...circuit contains anti freeze it should not be allowed to drain freely as it is pollutant It should be collected for possible reuse When draining after heat pump operation take care as the water may b...

Страница 8: ...ot equipped with pressure and temperature instruments so they need to be purchased by the user i All low positions of the water system should be provided with drainage ports to drain water in the evap...

Страница 9: ...f unit When ambient temperature lower 5 running cooling mode must be charged antifreeze Refer to upper parameters for the charged volume 0 5 10 15 20 25 Freezingpoint C Percentageof ethyleneglycol inw...

Страница 10: ...the rated power supply voltage for the unit for three phase units the unbalance between the phases must not exceed 3 If these parameters are not respected contact the electricity supply company For el...

Страница 11: ...y ACcontactor SWITCH Main control board Main control board If switch is closed the unit will be stopped forcibly Under this circumstance anti frozen protection and other protection functions are still...

Страница 12: ...wn has the highest priority In the status of remote shutdown other controllers can t start the unit SWITCH 2 If switch2 is closed the unit will shift to heating mode forcibly If switch2 breaks the uni...

Страница 13: ...ency of the compressor ON OFF and OK button 1 Press to confirm the former operation when finishing the setting work 2 Long press for 3S will recovers to factory default mode Mode choice function Funct...

Страница 14: ...quit force cooling mode The unit will enter power off mode automatically when quitting force cooling mode 2 Parameter query function To enter parameter query function Press and simultaneously for 3s...

Страница 15: ...ction Flow switch malfunction High temperature protection in heating mode Defrosting Oil return of compressor Remote control P4 P5 P6 P8 Pb C8 CH dF d0 d8 Compressor discharge temperature protection C...

Страница 16: ...huts down the compressor if the temperature measured by the heat exchanger outlet temperature sensor is less than 3 C The frost prevention temperature set point can be modified by an authorised servic...

Отзывы: