The choice and installation of components is the responsibility of the
installer who should follow good working practice and current
legislation. Before connecting the pipes, make sure they do not
contain stones, sand, rust, dross or other foreign bodies which might
damage the unit.Construction of a bypass is recommended to enable
the pipes to be washed through without having to disconnect the unit

(see drain valves). The connection piping should be supported in
such a way as to avoid it weighing on the unit.It is recommended
that the following devices are installed in the water circuit of the
evaporator.
A hydraulic safety valve shall be mounted in water system, which
 should open constantly.

If the installation requires a useful head higher than that obtained by
installing a pump assembly and storage tank, it is recommended that
an additional pump is installed on the unit. Provided the additional
pump installed inside of unit, the pump must connected  close to
plate heat exchanger. Provided the pump installed outside of unit,
the pump shall be connected at water pipe’s outlet.The pump can be
easily installed on the unit y removing the pump connection pipe.
Connect to terminal PL, PN on the electrical panel.

The chillers must be provided with a filling/top-up system
connected to the return line and a drain cock in the lowest part
of the installation.Installations containinganti-freeze or covered
by specific legislation must be fitted with hydraulic
disconnectors.

The manufactureris not liable for obstruction, breakage or noise
resulting from the failure to install filters or vibration dampers.
Particular types of water used for fillingor topping up must be
treated with appropriate treatment systems. For reference values,
see the table.

6

6. WATER PIPE INSTALLATION

.1 Connection drawing of pipeline system

1

Factory Connections

Installer Connections

A

F

WATER INLET

WATER OUTLET

3

4

7

2

5

6

8

9

10

10

11

12

14

13

11

6

9

9

1

Plate Heat Exchange

2

Differential Pressure Switch

3

Automatic Discharge Valve

4

Expansion Tank

5

Auto-watet replenishing

6

Circulating Pump

7

Pressure Gauge

8

Safety Valve

9

Drain/Chemical Washing Valve

10 Flexible Joint

11 Thermometer

12 Calibrating Valve

13 Y-shaped Filter

14 Water FlowSwitch

7

7

     In certain occasion (especially in manufacture cooling
process), for conforming the system water content requirement,
it’s necessary to mount a tank equipping with a cut-off baffle at the
system to avoid water short-circuit, Please see the following
schemes:

    kW is the unit for cooling capacity and L is the unit for G
water flow in the formula counting the minimum water flow.
Comfortable type air conditioner
G= cooling capacity×2.6L

6.2 Design of the tank in the system

The minimum chilled water flow is shown in the table 6-1

If the system flow is less than the minimum unit flow rate,
the evaporator flow can be recirculated, as shown in the
diagram.

6.3 Minimum chilled water flow

Evaporator

Recirculation

For minimum chilled water flow rate

Содержание IMCH-036KC-3

Страница 1: ...MINI CHILLER MAN IO IMCH 0615 intensity mx INSTALLATION OWNER S MANUAL IMCH 036KC 3 IMCH 060KC 3 3 and 5 Tons...

Страница 2: ...result in cutting injuries Never inspect or service the unit by yourself Ask a qualified service person to perform this work Do not dispose this product as unsorted municipal waste Collection of such...

Страница 3: ...ide Failure to observe could cause the chemicals to become deposited in the unit which could endanger the health of those who are hypersensitive to chemicals Do not place appliances which produce open...

Страница 4: ...LowPressureSwitch 12 DischargeGasthermistor 13 thermistor For Outdoor Temperature 14 Thermistor For EvaporationInHeating Thermistor For Condenser InCooling 15 Thermistor For PlateHeat Exchange1 16 The...

Страница 5: ...Never hold the inlet of the outdoor unit to prevent it from deforming 5 4 Water Outlet Reserve water outlet Reserve water outlet Water Outlet Outlet for power and connecting pipes Need to knock open...

Страница 6: ...containinganti freeze or covered by specific legislation must be fitted with hydraulic disconnectors The manufactureris not liable for obstruction breakage or noise resulting from the failure to insta...

Страница 7: ...circuit contains anti freeze it should not be allowed to drain freely as it is pollutant It should be collected for possible reuse When draining after heat pump operation take care as the water may b...

Страница 8: ...ot equipped with pressure and temperature instruments so they need to be purchased by the user i All low positions of the water system should be provided with drainage ports to drain water in the evap...

Страница 9: ...f unit When ambient temperature lower 5 running cooling mode must be charged antifreeze Refer to upper parameters for the charged volume 0 5 10 15 20 25 Freezingpoint C Percentageof ethyleneglycol inw...

Страница 10: ...the rated power supply voltage for the unit for three phase units the unbalance between the phases must not exceed 3 If these parameters are not respected contact the electricity supply company For el...

Страница 11: ...y ACcontactor SWITCH Main control board Main control board If switch is closed the unit will be stopped forcibly Under this circumstance anti frozen protection and other protection functions are still...

Страница 12: ...wn has the highest priority In the status of remote shutdown other controllers can t start the unit SWITCH 2 If switch2 is closed the unit will shift to heating mode forcibly If switch2 breaks the uni...

Страница 13: ...ency of the compressor ON OFF and OK button 1 Press to confirm the former operation when finishing the setting work 2 Long press for 3S will recovers to factory default mode Mode choice function Funct...

Страница 14: ...quit force cooling mode The unit will enter power off mode automatically when quitting force cooling mode 2 Parameter query function To enter parameter query function Press and simultaneously for 3s...

Страница 15: ...ction Flow switch malfunction High temperature protection in heating mode Defrosting Oil return of compressor Remote control P4 P5 P6 P8 Pb C8 CH dF d0 d8 Compressor discharge temperature protection C...

Страница 16: ...huts down the compressor if the temperature measured by the heat exchanger outlet temperature sensor is less than 3 C The frost prevention temperature set point can be modified by an authorised servic...

Отзывы: