Instrumentation Systems & Services MicroSpeed 196 Скачать руководство пользователя страница 5

Active Set Point

Set Point 1(3)1Set Point 2(4)

Set Point 3 & 4 Enable

Set Point 1

Open

Set Point 2

Closed

Open

Set Point 

3

Open

Open

Set Point 4

Closed

Closed

Closed

Set Point 3 & 4 Enable 

-

 Wiring of the 

Set Point 3 &4 Enable 

input is as follows:

TB1-9 (Set Point 3 & 4 Enable) 

to common (Open = Set Points 1 & 2 Enabled;

Closed = Set Points 3 & 4 Enabled).

Set Point 1(3)/Set Point 2(4)

 -

 Wiring of the 

Set Point 1(3)/Set Point 2(4) input

is as follows: 

TB1-16 (Set Point 1(3)/Set Point 2(4))

 t o common (Open = Set Point

l(3); Closed = Set Point  

2(4)).

Scroll Up/Scroll Down -

 

These inputs are used to make small changes to the active

set point while running. The high and low alarm outputs can be tied to these inputs,
preventing operators from running too fast or too slow. N.O. 

Momentary 

contacts

should be used when wiring the 

Scroll Up/ScrollDown

 inputs. The terminals are:

Scroll Up = TB1-6; Scroll Down = TB1-8.

WIRING  STATUS AND ALARM OUTPUTS:

The status and alarm outputs provide a completed circuit when a programmed result
occurs. (See 

“Status and Alarm Outputs” 

in Section VIII, 

“Programming Operational

Variables”). 

The outputs are Open Collector NPN transistors, rated for 5OVdc, 250mA

and .3-watt maximums.

These outputs are intended to be used with the Microspeed 196 inputs, relays, LEDs,
etc. Power to the output circuits should be wired parallel with the 

Diode Protect

(TB2-20)

 t erminal if inductive loads are driven, to avoid damage to the output

circuitry. (See Diagram 5: “Wiring Status and Alarm Outputs ”).

Diode Protect (TB2-20)

 -

 This is a protection circuit (back EMF diode). Input power

from the power supply should be wired in parallel with this terminal.

Drive Enable (TB2-16)

 -

 This output can be actuated under one of the three program-

mable conditions. 

Drive Enable 

is used to give the MicroSpeed  196 control over the

Run/Stop  command on the drive, or on other MicroSpeed  units.

L

OW 

Alarm (TB2-19)

 -

 If the shaft speed drops below this programmed setting, the

output will conduct in order to actuate a load.

High Alarm (TB2-17)

 -

 If the shaft speed goes above this programmed setting, the

output will conduct in order to actuate a load.

Deviation Alarm (TB2-14)

 -

 This output is active in the Follower mode. If the

follower shaft is ahead or behind the Master exceeding the value programmed, the
output will actuate the load.

Ramp Complete (TB2-13)

 -

 This is a nonprogrammable output. This output is

actuated when the Speed Set Point selected is reached (Master mode only).

Zero Speed (TB2-11)

 -

 This is a nonprogrammable output. This output is actuated

when there is no feedback present, i.e., when the motor or shaft rotation has stopped,
or feedback is lost, due to an external problem.

7

Diagram 5

Wiring Status and Alarm Outputs:

8

Содержание MicroSpeed 196

Страница 1: ...MSMAN32C MicroSpeed 196...

Страница 2: ...is designed in sequential order from basics to the highest level of MicroSpeed 196 programming The deeper you read into each section the less relevent the options may be to your application If this is...

Страница 3: ...d to the wiper of the speed potentiometer The isolated common terminal on the MicroSpeed 196 is connected to reference common on the drive Terminal locations are as follows TB2 2 Isolated Command Outp...

Страница 4: ...ignal from a PLC The MicroSpeed 196 only reads this input while stopped in the Ready mode Wiring of the Master Follower input is as follows TB1 15 Master Follower to common Open Master Closed Follower...

Страница 5: ...puts relays LEDs etc Power to the output circuits should be wired parallel with the Diode Protect TB2 20 terminal if inductive loads are driven to avoid damage to the output circuitry See Diagram 5 Wi...

Страница 6: ...display will prompt for a variable number and the numeric display will indicate two zeros 00 which will reflect the variable number entered Enter the desired variable number and press ENTER If you are...

Страница 7: ...FOLLOWER MODE The Microspeed 196 in the Follower mode mirrors a lead frequency input and can be scaled by the Ratio Set Point The lead frequency is typically generated from a digital transducer on ano...

Страница 8: ...can be independently locked The section of the keypad that is locked is determined by placing a 1 one in the appropriate location Any section or combination of sections can be locked See chart below...

Страница 9: ...ART MIN 56 PARTSIHR 57 Percent 58 RATIO 65 Customized 15 Diagnostic 0 Custom User Unit Labels If the choices presented in Variable 10 do not provide the display that is needed a Custom User Unit Label...

Страница 10: ...ect the proper polarity of the Command Output Voltage using the Forward Reverse Input Open Positive Closed Negative 3 Access Diagnostic 9 Digital Potentiometer by pressing 2nd Function key then the 9...

Страница 11: ...ters at the unstable speed 19 FOLLOWER MODE PID CONSIDERATIONS Variable 09 Max Lead Wind Up If you are speed matching and have very fast master speed changes or if you are bringing the Follower motor...

Страница 12: ...ill decrease motor speed Variable 28 Auxiliary Input Delay Delays the start of the Auxiliary Trim function on startup Enter the number of 10 msec update cycles to wait When ENTER is pressed the MicroS...

Страница 13: ...g inputs Closed Open Loop Master Follower Forward Reverse Keypad Unlocked Locked out Set Point 1 3 2 4 Set Point 3 4 Disabled Set Point 3 4 Enabled No Scroll Scroll Down No Scroll Scroll Up Left to ri...

Страница 14: ...oSpeed 196 with node address 01 will be the only MicroSpeed 196 to answer the host computer but all MicroSpeed 196 s will respond to global commands Never duplicate an address on the same communicatio...

Страница 15: ...ommunication Valid characters from the host are 0 command 1 read variable or 2 write variable The MicroSpeed 196 will echo the host in this character location unless the host communication message has...

Страница 16: ...in a message it will respond with a 3 in the Character 4 position The type of error will be specified in the Character 6 position Error type Problem 1 Parity Error Standard Definition 2 Data Error Da...

Страница 17: ...aximum Speed PPR Maximum Lead RPM Lead PPR User Unity Ratio Master Follower The active set point will only change with a Change Set Point command A write command to the active set point while running...

Страница 18: ...mp Compete Zero Speed Deviation Drive Enable Operational Specifications Accuracy Respons Modes of Operation Preset Speeds Accel Decel Times Processor Speed Display Alphanumeric Display Function LEDs D...

Страница 19: ......

Отзывы: