devices to safely provide power to all devices. Observe the following guidelines:
•
Balance the server power load between available AC supply branch circuits.
•
Do not allow the overall system AC current load to exceed 80 percent of the branch circuit
AC current rating.
•
Do not use common power outlet strips for this equipment.
•
Provide a separate electrical circuit for the server.
5.1.4 Electrical Grounding Requirements
The server must be grounded properly for optimal operation and safety. In the United
States, you must install the equipment in accordance with NFPA 70, 1999 Edition (National
Electric Code), Article 250, as well as any local and regional building codes.
In Canada, you must install the equipment in accordance with Canadian Standards
Association, CSA C22.1, and Canadian Electrical Code. In all other countries, you must
install the equipment in accordance with any regional or national electrical wiring codes,
such as the International Electrotechnical Commission (IEC) Code 364, parts 1 through 7.
Furthermore, you must be sure that all power distribution devices used in the installation,
such as branch wiring and receptacles, are listed or certified grounding-type devices.
Because of the high ground-leakage currents associated with multiple servers connected to
the same power source, Inspur recommends the use of a PDU that is either permanently
wired to the building’s branch circuit or includes a nondetachable cord that is wired to
an industrial-style plug. NEMA locking-style plugs or those complying with IEC 60309 are
considered suitable for this purpose. Using common power outlet strips for the server is not
recommended.
5.2 Rack Warnings
WARNING:
To reduce the risk of personal injury or damage to the equipment, please be
sure of the following:
•
The leveling jacks are extended to the floor.
• The full weight of the rack rests on the leveling jacks.
Содержание TS860M5
Страница 1: ...Inspur Server User Manual TS860M5 ...
Страница 40: ...34 CAUTION Please route the cables according to the purchased machine configuration ...
Страница 90: ...84 ...
Страница 94: ...88 9 7 BMC Settings Select BMC Settings on the navigation tree to open the BMC Settings interface It contains ...
Страница 96: ...90 ...
Страница 97: ...BMC Settings 91 ...
Страница 99: ...BMC Settings 93 ...
Страница 102: ...96 Restore factory defaults To restore BMC s configuration to factory state ...
Страница 103: ...BMC Settings 97 ...
Страница 104: ...98 ...