5 Parameter Table
- 31 -
Para� No� Para� Name
Setting Range
Unit
Default
Property
F4-23
AI2 min� Input
-11�00 to 11�00 V
0�01 V
0�02 V
☆
F4-24
AI2 min� Inp frequency
-100�0% to 100�0%
0�1%
0�0%
☆
F4-25
AI2 max� Input
-11�00 to 11�00 V
0�01 V
10�00 V
☆
F4-26
AI2 max� Input frequency
-100�0% to 100�0%
0�1%
100�0%
☆
F4-27
AI2 filter time
0�000s to 10�000s
0�001s
0�005s
☆
F4-28
AI3 min� Input
-11�00 to 11�00 V
0�01 V
0�02 V
☆
F4-29
AI3 min� Input frequency
-100�0% to 100�0%
0�1%
0�0%
☆
F4-30
AI3 max� Input
-11�00 to 11�00 V
0�01 V
10�00 V
☆
F4-31
AI3 max� Input frequency
-100�0% to 100�0%
0�1%
100�0%
☆
F4-32
AI3 filter time
0�000s to 10�000s
0�001s
0�000s
☆
F4-43
AI1 Display value 1
-9�999 to 9�999 V
0�001 V
2�000 V
☆
F4-44
AI1 measured value 1
-9�999 to 9�999 V
0�001 V
2�000 V
☆
F4-45
AI1 Display value 2
-9�999 to 9�999 V
0�001 V
8�000 V
☆
F4-46
AI1 measured value 2
-9�999 to 9�999 V
0�001 V
8�000 V
☆
F4-47
AI2 Display value 1
-9�999 to 9�999 V
0�001 V
2�000 V
☆
F4-48
AI2 measured value 1
-9�999 to 9�999 V
0�001 V
2�000 V
☆
F4-49
AI2 Display value 2
-9�999 to 9�999 V
0�001 V
8�000 V
☆
F4-50
AI2 measured value 2
-9�999 to 9�999 V
0�001 V
8�000 V
☆
F4-51
AI3 Display value 1
-9�999 to 9�999 V
0�001 V
2�000 V
☆
F4-52
AI3 measured value 1
-9�999 to 9�999 V
0�001 V
2�000 V
☆
F4-53
AI3 Display value 2
-9�999 to 9�999 V
0�001 V
8�000 V
☆
F4-54
AI3 measured value 2
-9�999 to 9�999 V
0�001 V
8�000 V
☆
Group F5: Output Terminals
F5-01
T/a1-t/b1-t/c1 function selection
0: no function
1: drive is running
2: fault output
3 to 5: reserved
6: motor overload warning
7: drive overload warning
8 to 11: reserved
12: time is out
13 to 14: reserved
15: drive is ready
16: abs AI1 value is bigger than abs AI2 value
after correction
17 to 19: reserved
20: communication control
21 to 22: reserved
23: Displacement switch of dual displacements
piston pump (normally open)
24: pressure control (normally close)
25: slave pump warning
26: Displacement switch of dual Displacements
piston pump (normally open)
27: DC bus voltage established
28: business preset running time out
29: business preset running time less than 24
hours
30: maximum reverse speed
31: warning
32: KTY temperature reached
1
2
☆
F5-02
T/a2-t/c2 function selection
1
23
☆
F5-03
DO1 function selection
1
24
☆