5 Parameter Table
- 28 -
Para� No� Para� Name
Setting Range
Unit
Default
Property
Group F1: Motor Parameters
F1-00
Motor type selection
0: induction motor
1: frequency variable induction motor
2: PMSM
1
2
★
F1-01
Rated power
0�4 to 1000�0 kW
0�1 kW
Model
dependent
★
F1-02
Rated voltage
0 to 480 V
1 V
Model
dependent
★
F1-03
Rated current
0�0 to 6500�0 A
0�1 A
Model
dependent
★
F1-04
Rated frequency
0�00 Hz to F0-10
0�01 Hz
Model
dependent
★
F1-05
Rated rotating speed
0 to 30000 rpm
1 rmp
Model
dependent
★
F1-11
D-axis inductance
0 to 65�535 mH
0�001 mh
Model
dependent
★
F1-12
Q-axis inductance
0 to 65�535 mG
0�001 mh
Model
dependent
★
F1-13
Stator resistance
0 to 65�535
0.001 Ω
Model
dependent
★
F1-14
Motor manufacturer selection
0: none 1: manual
motor angle input (A1-02)
2: reserved
3: Inovance motor
4: PHASE motor
5: HAI TIAN motor
1
0
☆
F1-15
Back-EMF
0 to 65535 V
1 V
Model
dependent
★
F1-16
Motor auto-tuning method selection
0: no auto-tuning
1: no-load static
2: no-load dynamic, reverse running fast
3: with-load static
4: with-load dynamic, reverse running fast
5: no-load dynamic, forward running fast
6: no-load dynamic and short time, forward
running fast
1
0
★
Group F2: Vector Control
F2-00
Speed loop proportional gain kp1
1 to 400
1
60
☆
F2-01
Speed loop integral gain ki1
0�01s to 10�00s
0�01s
0�3s
☆
F2-02
Switching frequency 1 for speed loop
gains
0�00 Hz to F2-05
0�01 Hz
5�00 Hz
☆
F2-03
Speed loop proportional gain kp2
1 to 400
1
60
☆
F2-04
Speed loop integral gain ki1
0�01s to 10�00s
0�01s
0�3s
☆
F2-05
Switching frequency 2 for speed loop
gains
F2-02 to F0-10
0�01 Hz
10�00 Hz
☆
F2-07
Speed loop filter time
0�5 to 10�0 ms
0�1 ms
1�0 ms
☆
F2-08
Torque upper limit enable
0: speed control
1: torque control
0
0
☆