4 Quick Setup
- 21 -
Continued
Para�
Parameter name
Default
Commissioning
Set AI1 range: pressure command
F4-18
AI curve 1 minimum input
0�00
0�00
-11�00 to11�00 v;
F4-19
Corresponding setting of AI1minimum
input
0�0
0�0
-100�0% to 100�0%
Note
: 0v pressure command is designed by press plc to represent 0%
pressure�
F4-20
AI1 maximum input
10�00
5�00
-11�00 to 11�00 v
F4-21
Corresponding setting of AI1maximum
input
100�0
100�0
-100�0% to 100�0%
Set AI2 range: flow command
F4-23
AI curve 2 minimum input
0�00
0�00
-11�00 to11�00 v;
F4-24
Corresponding setting of AI2 minimum
input
0�0
0�0
-100�0% to 100�0%
F4-25
AI2 maximum input
10�00
10�00
-11�00 to 11�00 v
F4-26
Corresponding setting of AI2 maximum
input
100�0
100�0
-100�0% to 100�0%
Set AI3 range: pressure feedback
F4-28
AI curve 3 minimum input
0�00
0�00
-11�00 to11�00 v;
F4-29
Corresponding setting of AI3minimum
input
0�0
0�0
-100�0% to 100�0%
F4-30
AI3 maximum input
10�00
10�00
-11�00 to 11�00 v
F4-31
Corresponding setting of AI3maximum
input
100�0
100�0
-100�0% to 100�0%
Note
: 10v pressure feedback represents 100% pressure feedback� This is
related to A3-03�
Note
: AI 1 is fixed as pressure command input, AI2 is fixed as speed/flow command input, and AI3 is fixed as pressure sensor
feedback input. This configuration can’t be changed!
Continued
Para�
Parameter name
Default
Commissioning