Group A3: Motor 3 Parameters
Function
code
Parameter Name
Setting Range
Unit
Default
Commission
A3- 00
Motor type selection
0: Common asynchronous motor
1: Variable frequency asynchronous motor
N.A
0
A3- 01
Rated motor power
0.1 to 30.0
kW
Model
dependent
A3- 02
Rated motor voltage
1 to 1000
V
Model
dependent
A3- 03
Rated motor current
0.01 to 655.35
A
Model
dependent
A3- 04
Rated motor frequency 0.01 to maximum frequency
Hz
Model
dependent
A3- 05
Rated motor rotational
speed
1 to 65535
RPM
Model
dependent
A3- 06
Stator resistance
0.001 to 65.535
Ω
Model
dependent
A3- 07
Rotor resistance
0.001 to 65.535
Ω
Model
dependent
A3- 08
Leakage inductive
reactance
0.01 to 655.35
mH
Model
dependent
A3- 09
Mutual inductive
reactance
0.1 to 6553.5
mH
Model
dependent
A3- 10
No-load current
0.01 to A3- 03
A
Model
dependent
A3- 37
Auto-tuning selection
0: No auto-tuning
1: Static auto-tuning
2: Complete auto-tuning
N.A
0
A3- 38
Speed loop
proportional gain 1
0 to 100
N.A
30
A3- 39
Speed loop integral
time 1
0.01 to 10.00
s
0.50
A3- 40
Switchover frequency
1
0.00 to A3- 43
Hz
5.00
A3- 41
Speed loop
proportional gain 2
0 to 100
N.A
15
A3- 42
Speed loop integral
time 2
0.01 to 10.00
s
1.00
A3- 43
Switchover frequency
2
A3- 40 to maximum output frequency
Hz
10.00
A3- 44
Vector control slip gain 50 to 200
%
100
A3- 45
Time constant of
speed loop filter
0.000 to 0.100
s
0.000
A3- 46
Vector control
over-excitation gain
0 to 200
N.A
64
A3- 47
Torque upper limit
source in speed
control mode
0 to 7
N.A
0
A3- 48
Digital setting of torque
upper limit in speed
control mode
0.0 to 200.0
%
150.0
A3- 51
Excitation adjustment
proportional gain
0 to 20000
N.A
2000
A3- 52
Excitation adjustment
integral gain
0 to 20000
N.A
1300
A3- 53
Torque adjustment
proportional gain
0 to 20000
N.A
2000
A3- 54
Torque adjustment
integral gain
0 to 20000
N.A
1300