Function
code
Parameter Name
Setting Range
Unit
Default
Commission
F5-22
DO active mode
selection
7-segment
0
0
0
0
0
N.A
00000
DO2 active mode:
0: Positive logic
1: Negative logic
DO1 active mode:
0: Positive logic
1: Negative logic
Relay 2 active mode:
0: Positive logic
1: Negative logic
Relay 1 active mode:
0: Positive logic
1: Negative logic
FMR active mode
0: Positive logic
1: Negative logic
☆
: ‘Positive logic’ means that, DO output terminal is normally the default state.
‘Negative logic’ means the opposite situation.
Step 10: Set Startup Frequency If Needed
Function
code
Parameter Name
Setting Range
Unit
Default
Commission
F6-03
Startup frequency
0.00 to 10.00
Hz
0.00
F6-04
Startup frequency
active time
0.0 to 100.0
s
0.0
Step 11: Set S-Curve If Needed
Function
code
Parameter Name
Setting Range
Unit
Default
Commission
F6-07
Acceleration/
Deceleration mode
0: Linear mode
1: S-curve mode A
2: S-curve mode B
N.A
0
1
F6-08
Time proportion of
S-curve start segment
0.0 to [100.0 minus F6-09]
%
30.0
F6-09
Time proportion of
S-curve end segment
0.0 to [100.0 minus F6-08]
%
30.0