INOVA AUTOMATION
NICE Series Integrated Elevator Solution
–
N Quick Start-Up Guide V1.0
33
Once door operator function is completed successfully, Elevator is ready for Normal operation with rated
speed
After completion of Door operator commissioning and N shaft learning process, Lift is ready for
normal operation. Now the lift car will be located in top most floor terminal level and the corresponding input
terminal sequence will be seen in the NICE1000 Main Control Board LEDs as shown in the below table
Functional Sequence for Auto door operation at Main Control Board (MCB)
Door Close Command (Y7 relay gets ON)
Feed Back Signal
Door Fully opened
Door In between
Door Fully Closed
Remark
DOL
DCL
X14
ON
X18
OFF
X14
OFF
X18
OFF
X14
OFF
X18
ON
Improper Sequence can
lead to Err53
If DOL is not detected
even after door protection
time, gives Err55
Landing Door Safety
Car Door Safety
X26
OFF
X27
OFF
X26
OFF
X27
OFF
X26
ON
X27
ON
Door Open Command (Y6 relay gets ON)
Feed Back Signal
Door Fully Closed
Door In between
Door Fully opened
Remark
DOL
DCL
X14
OFF
X18
ON
X14
OFF
X18
OFF
X14
ON
X18
OFF
Improper Sequence can
lead to Err53
If DOL is not detected
even after door protection
time, gives Err55
Landing Door Safety
Car Door Safety
X26
ON
X27
ON
X26
OFF
X27
OFF
X26
OFF
X27
OFF
6.2.3.
Manual Door Setup Procedure
Follow the N wiring diagram for manual door operation
Enable Bit0=1 of A1-00 for manual door operation
Retiring cam contactor (RCR) will be operated through
‘
Y6
’
relay of MCB, program Y6 relay as F7-06=30
RCR contactor
‘
NC
’
feedback will be connected to X19 of MCB
Disable Door Open Limit (DOL), Door Close Limit (DCL), Door Sensor and Door open Button function using
F5-14=0, F5-18=0, F5-15=0 and F6-12=0