INOVA AUTOMATION
NICE Series Integrated Elevator Solution
–
N Quick Start-Up Guide V1.0
30
5.9
Inspection Running
Now the Lift is ready for Inspection running.
Please refer content of 5.6 fo
r MCB’s LED sequence for
Inspection operation
Make sure that
all safety switches are connected and functioning
properly
Make sure that the
Up & Down terminal Limit and terminal slowdown switches
are wired up and
located in the right position as given in the manual
Use the UP and DOWN Button in the Inspection board on controller/Car-Top to run the lift in Inspection
speed.
Check the direction of the lift running.
X5 LED
in the Main Control Board (MCB) glows when
UP button
is
pressed. During this time, lift should run in
UP direction
and for
DOWN button
,
X6 LED
glows
and lift
runs in
Down direction
.
If the
running direction is wrong
, then modify the parameter
F2-10(0
↔
1, 1
↔
0)
If
Err20
comes after some distance travelled in Inspection mode, refer the error history for remedies