INOVA AUTOMATION
NICE Series Integrated Elevator Solution
–
N Quick Start-Up Guide V1.0
25
5.6
Input terminal LED Sequence for Main Control Board (MCB) while Initial start-Up
Type of Input
Input
Terminal
LED
status
Parameter
Value
Contact
Type
Remarks
Running Contactor Feedback (SW)
X2
ON
F5-02=104
NC
If
X2 LED off
, then the drive
gives
Err36
while start
Brake Contactor Feedback (BY)
X3
ON
F5-03=105
NC
If
X3 LED off
, then the drive
gives
Err37
always
Inspection mode input signal
X4
OFF
F5-04=109
NC
OFF
Inspection mode
ON
Normal Mode
Inspection mode UP signal
X5
OFF
F5-05=10
NO
For UP direction command in
INS mode
Inspection mode DOWN signal
X6
OFF
F5-06=11
NO
For DOWN direction command
in INS mode
UP direction limit signal
X9
ON
F5-09=115
NC
UP and Down Limit and Slow
down Switches must be
connected for Inspection run
and for motor tuning
Down direction limit signal
X10
ON
F5-10=116
NC
Up terminal slowdown signal
X11
ON
F5-11=117
NC
Down terminal slowdown signal
X12
ON
F5-12=118
NC
FX-Shorting Contactor Feedback
signal
X19
ON
F5-19=107
NC
Applicable for PMSM Gearless
machine.
Err29 if X19
LED is
OFF
Rescue function-UPC contactor
Feedback Signal
X22
ON
F5-22=133
NC
Applicable for UPS mode
Rescue is enabled
Safety Circuit feedback signal
(110VAC Input)
X25
ON
F5-25=01
NO
If all the field safety circuits are
not ok and
X25 LED is OFF
,
then the display shows
Err41
Door lock safety circuit feedback
signal1(Landing Door)
(110VAC
Input)
X26
ON
F5-26=02
NO
If all Landing doors are safely
closed, then X26 LED gets
ON
Door lock safety circuit feedback
signal2(Car Door)
(110VAC
Input)
X27
ON
F5-27=03
NO
If car door is safely closed, then
X27 LED gets
ON