3. Elevator Hoistway Switches and Sensor Installation
3.1 Terminal floor switches mounting position
In the formula, "L" indicates the slow-down distance, "V" indicates the F0-04 (Rated elevator speed), and "F3-08"
indicates the special deceleration rate.
The default value of F3-08 (Special deceleration rate) is 0.5 m/s2. The slow-down distances calculated based on
different rated elevator speeds are listed in the following table:
Rated Elevator Speed (F0-04) m/s
0.4
0.5
0.63
0.75
1.0
1.5
1.75
Distance Slow-down switch (m)
0.5-0.6
0.6-0.8
0.8-1.0
0.9-1.2
1.2-1.6
1.8-2.5