25
Err.31
Loss of the PID
reversal signal
The PID signal reversal is lower than the
instruction value E2.11
Check the PID return signal or set E2.11
with an appropriate value
Err.40
Defect of the
current limit
cycle by cycle
1. The load is too high or a motor blocking
happens
2.The model inverter is too weak
1. Reduce the load and check the motor
2. Chose an inverter model more
powerful
Err.41
Defect of the
change of the
direction
rotation during
the functioning
Request to change the direction of rotation
too fast for the terminal block
Change the direction of rotation before
the motor stops
Err.42
Speed
difference
defect
1. The setting of a too large deviation of
speed parameters (F8.15, F8.16) is
unreasonable.
2. The setting of the coder parameters is
incorrect
3. Parameters were not identified
Set the detection parameters of the
coder on correct values
Err.43
Overspeed of
the motor
1. The setting is not done
2. The setting of the coder parameters is
incorrect
3. Parameter to detect the motor speed
(F8.13, F8.14) is extreme
1. Configure the motor
2. Configure correctly the coder
3. Set the detection parameters on an
appropriate range.
Err.45
Overheating of
the motor
1. The temperature sensor cable is
disconnected
2. The motor temperature is too high
1. Check the probe cable
2. Reduce the running time cool the
motor down in an other way to
Err.51
Error of initial
position
The difference between the motor
parameters and the actual parameters is to
big
Check if the motor parameters set are
correct
iNORéA Automation & Control Solution Provider
www.inorea.com
Содержание VFR-091
Страница 6: ...6 From 11KW to 160KW ...