This parameter defines 4 different modes to control the inverter functioning by input terminal blocks.
0: Two electric wires type 1
This mode is the most used. The function FWD / REV of the motor is determined by DI1, DI2.
The terminal function is set like that:
Terminal block input
Value to be chosen
Description
DI1
1
(FWD)
DI2
2
(REV)
DI1 and DI2 are the multifunction input from DI1 to DI6.
Setting:
F0.11=4 (Inverter control by terminal block + keyboard)
F1.10=0 (Two electric wires type 1)
F1.00=1 (DI1 FWR)
F1.01=2 (DI2 REV)
1:
Two electric wires type 2
In this case, DI1 allows the rotation and the forward direction, while DI2 is used to activate the reverse direction.
The terminal function is set like that:
Terminal block input
Value to be chosen
Description
DI1
1
(FWD)
DI2
2
(REV)
DI1 and DI2 are the multifunction input from DI1 to DI6.
K1
K2
Control
0
0
Stop
0
1
Stop
1
0
(FWD)
1
1
(REV)
Setting:
F0.11=4 (Inverter control by terminal block + keyboard)
F1.10=0 (Two electric wires type 2)
F1.00=1 (DI1 FWR)
F1.01=2 (DI2 REV)
K1
K2
Control
0
0
Stop
0
1
(FWD)
1
0
(REV)
1
1
Stop