INOR IPAQ C520 Скачать руководство пользователя страница 4

1

 INTRODUCTION 

IPAQ C520/R520

www.inor.com

02/2019 - 86B520S001 - AD 520 SIL R1.4 en

1.4  Relevant standards / Literature

This "Safety manual" is a complement to the regular Handbook(User Instructions) for IPAQ C520 
and R520.
In addition to the safety rules in this documentation, national and regional safety rules and 
industrial safety regulations must also be observed.

Standard

Designation

IEC 61508:2010

all parts

Functional safety of electrical/electronic/programmable electronic safety related systems 

 

Part 2: Requirements for electrical/electronic/programmable electronic safety-related 

systems

IEC 61326-3-1:2008

EN 61326-3-1:2008

Immunity requirements for safety-related systems and for equipment intended to perform 

safety-related functions (functional safety)- General industrial applications

Namur NE 21

Electromagnetic compatibility of industrial process and laboratory control equipment

Namur NE 32

Data retention in the event of a power failure in field and control instruments with 

microprocessors

Namur NE 43

Standardization of the signal level for the failure information of digital transmitters

Namur NE 53

Software of field devices and signal processing devices with digital electronics

Namur NE 79

Microprocessor equipped devices for safety instrumented systems

Namur NE 89

Temperature transmitter with digital signal processing

Namur NE 107

Self-monitoring and diagnosis of field devices

EN 60079-0:2009

EN 60079-0:2012

Electrical apparatus for explosive gas atmospheres - Part 0: General requirements

EN 60079-11:2007

EN 60079-11:2012

Explosive atmospheres - Equipment protection by intrinsic safety "i"

EN 60079-26:2007

EN 60079-26:2015

Explosive atmospheres -  Part 26: Equipment with equipment protection level (EPL) Ga

Table 1-1: Supported standards during the development of C520/R520

Содержание IPAQ C520

Страница 1: ...l SIL Safety manual SIL Safety manual SIL Safety manual SIL IPAQ C520 R520 IPAQ C520 R520 IPAQ C520 R520 IPAQ C520 R520 Supplementary Instructions Supplementary Instructions Supplementary Instructions...

Страница 2: ...safety function 8 4 3 Redundancy 9 4 3 1 Sensor drift 10 4 3 2 Sensor backup 10 5 Project planning 11 5 1 Applicable device documentation 11 5 2 Project planning behaviour during operation and malfun...

Страница 3: ...Institute of Sweden AB former SP Technical Research Institute of Sweden Remote configuration with process control system PC or HART hand terminal is not not not not possible in combination with SIL a...

Страница 4: ...mur NE 21 Electromagnetic compatibility of industrial process and laboratory control equipment Namur NE 32 Data retention in the event of a power failure in field and control instruments with micropro...

Страница 5: ...de on a safety related system is greater than one per year and greater than twice the proof check frequency MTBF Mean Time Between Failure is average time between failure occurrences MTTR Mean Time To...

Страница 6: ...r Hence the connection end of the T C cold junction constitutes a temperature reference or base value that has to be measured in order to determine the temperature at the critical spot hot junction Th...

Страница 7: ...transmitter which improves predicting problems within the industrial safety instrumented systems SIS reducing the manual testing The C520 R520 is a modular and configurable system with the ability to...

Страница 8: ...t a demand from the process Safe failures are divided into safe detected SD and safe undetected SU failures Fail Dangerous A dangerous failure is defined as a failure of the temperature transmitter C5...

Страница 9: ...ted To prevent a safety system from restart due to the toggling output the system should be setup so that once an alarm signal has occurred from the safety loop the system shouldn t go back to normal...

Страница 10: ...o the other sensor and the output signal will reflect the measured value of that sensor A diagnostic message is transmitted via HART to the PLC If the Average function is activated in the configuratio...

Страница 11: ...nt accuracy in SIL mode a hardware error influencing the measured value will result in a system error signal if the measured signal deviates more than 2 of selected input span System Error Detection T...

Страница 12: ...rements Up to 99 of the internal failures shall be detected via the proof tests The input to the SIL transmitter is simulated and tested for the internal errors in the hardware and the firmware Proof...

Страница 13: ...field and date of the test 8 2 Specify any other information in the message field Table 6 1 Proof test configuration for the SIL transmitters Step Description Step Description Yes No Comments 1 Conne...

Страница 14: ...e is 24 hours For safety applications only the 4 20 mA output was considered The HART protocol at C520 R520 is only used for setup and diagnostic purpose not during safety operation mode The failure r...

Страница 15: ...f 0 the SFF shall be 90 for SIL 2 SIFs according to table 3 of IEC 61508 2 Under the assumptions described in the chapter before and the definitions given in chapter Desription of the failure categori...

Страница 16: ...e PFDavg respectively the PFH values do not fulfill the requirements for SIL 2 of table 2 3 of IEC 61508 1 Failure category SFF PFDavg at Tproof PFH SIL AC SD SU DD DU FIT 1 year 2 years 5 years 10 ye...

Страница 17: ...that the PFDavg respectively the PFH values do not fulfill the requirements for SIL 2 of table 2 3 of IEC 61508 1 Failure category SFF PFDavg at Tproof PFH SIL AC SD SU DD DU FIT 1 year 2 years 5 year...

Страница 18: ...espectively the PFH values do not fulfill the requirements for SIL 2 of table 2 3 of IEC 61508 1 Failure category SFF PFDavg at Tproof PFH SIL AC SD SU DD DU FIT 1 year 2 years 5 years 10 years Close...

Страница 19: ...es marked in dark grey indicate that the PFDavg respectively the PFH values do not fulfill the requirements for SIL 2 of table 2 3 of IEC 61508 1 Failure category SFF PFDavg at Tproof PFH SIL AC SD SU...

Страница 20: ...8 APPENDIX 20 IPAQ C520 R520 www inor com 02 2019 86B520S001 AD 520 SIL R1 4 en 8 1 Declaration of conformity for Functional Safety SIL...

Страница 21: ...APPENDIX 8 21 IPAQ C520 R520 www inor com 02 2019 86B520S001 AD 520 SIL R1 4 en 8 2 exida FMEDA management summary...

Страница 22: ...8 APPENDIX 22 IPAQ C520 R520 www inor com 02 2019 86B520S001 AD 520 SIL R1 4 en...

Страница 23: ...APPENDIX 8 23 IPAQ C520 R520 www inor com 02 2019 86B520S001 AD 520 SIL R1 4 en...

Страница 24: ...8 APPENDIX 24 IPAQ C520 R520 www inor com 02 2019 86B520S001 AD 520 SIL R1 4 en 8 3 Type Examination Certificate...

Страница 25: ...APPENDIX 8 25 IPAQ C520 R520 www inor com 02 2019 86B520S001 AD 520 SIL R1 4 en...

Страница 26: ...in step 4 Proof test check points Send goods including this document to Company Address Contact person Telephone Fax Email Product ID Serial no Reason for the return maintenance Have you performed the...

Страница 27: ...NOTES 9 27 IPAQ C520 R520 www inor com 02 2019 86B520S001 AD 520 SIL R1 4 en...

Страница 28: ...82 762 2 E mail info inor gmbh de Web www inor gmbh de The current list of all INOR contacts and addresses can be found at www inor com Inor Process AB PO Box 9125 SE 200 39 Malm Sweden Phone 46 0 40...